Lenovo ThinkServer RD430 Hardware Maintenance Manual page 176

Hardware maintenance manual - thinkserver rd430
Hide thumbs Also See for ThinkServer RD430:
Table of Contents

Advertisement

2. If the server is installed in a rack cabinet, remove the server from the rack cabinet and place it on a flat,
clean, and static-protective surface. See the Rack Installation Instructions that comes with the server.
3. Remove the server cover. See "Removing the server cover" on page 83.
4. Locate the riser card assembly 2. See "Server components" on page 31.
5. Grasp the riser card assembly 2 by its edges and carefully lift it straight up and off the chassis.
Note: If there is any cable connected to any PCI Express card on the riser card assembly 2, you might
need to remove the cooling shroud first. See "Removing and reinstalling the cooling shroud" on page 91.
Figure 121. Lifting the riser card assembly 2 off the chassis
6. If necessary, disconnect any cables from the PCI Express cards installed on the riser card assembly 2
and then completely remove the riser card assembly 2 out of the chassis.
7. Touch the static-protective package that contains the new riser card assembly 2 to any unpainted
surface on the outside of the server. Then, remove the new riser card assembly 2 from the package.
8. Remove the PCI Express cards (if any) from the old riser card assembly 2 and install them on the new
one. See "Installing or removing an Ethernet card" on page 114.
9. If necessary, reconnect any cables to the PCI Express cards on the new riser card assembly 2.
162
ThinkServer RD430 Hardware Maintenance Manual