OUTDOOR VENTING

When installed outdoors the Futera II must be fi tted with
the factory supplied outdoor hood, air intake adapter with
fi lter. Horizontal discharge tee supplied by others, see
Figure 10. Multiple units must be spaced per Figure 11 to
prevent fl ue gases from being ingested by adjacent units.
The boiler/water heater must be at least 10 ft, 3.1 m from
any door, window or gravity air inlet into any building and
at least 3 ft, 0.9 m from any overhang unless local codes
dictate differently.
Figure 10 – Outdoor Venting
24"
.6 m
Avoid locations where wind deflection off of adjacent
walls, buildings or shrubbery might cause a downdraft.
The unit(s) should be located at least 3 ft, 0.9 m from
structures. Outdoor installations are not recommended in
areas where the danger of snow blockage exists.
CAUTION: Do not place the boiler/water heater in a
location that would subject it to runoff from adjacent
buildings or damage may occur voiding the warranty!
Figure 11 – Multiple Outdoor Units