Timing - National Instruments DAQ PCI-1200 User Manual

Daq multifunctional i/o board for pci bus computers
Hide thumbs Also See for DAQ PCI-1200:
Table of Contents

Advertisement

Timing

© National Instruments Corporation
The PCI-1200 generates an interrupt in the following five cases (each of
these interrupts is individually enabled and cleared):
When a single A/D conversion can be read from the A/D FIFO
memory.
When the A/D FIFO is half-full.
When a DAQ operation completes, including when either an
OVERFLOW or an OVERRUN error occurs.
When the digital I/O circuitry generates an interrupt.
When a rising edge signal is detected on the DAC update signal.
The PCI-1200 uses two 82C53 counter/timer integrated circuits for internal
DAQ and DAC timing and for general purpose I/O timing functions.
Figure 4-3 shows a block diagram of both groups of timing circuitry
(counter groups A and B).
4-3
Chapter 4
Theory of Operation
PCI-1200 User Manual