QuickSpecs
Configuration
a. In line connector is available from HP by purchasing A6440A, Option 401.
b. Panel mount receptacles must be purchased by the customer from a local Mennekes supplier.
c. In line connector is available from HP by purchasing A6440A, Option 501.
NOTE: A qualified electrician must wire the PDCA in line connector to site power using copper wire and in compliance
NOTE:
NOTE:
NOTE:
with all local codes.
Input Requirements
Input Requirements
Input Requirements
Input Requirements
Reference the Site Preparation Guide for detailed power configuration requirements.
Cooling Requirements
Cooling Requirements
Cooling Requirements
Cooling Requirements
PDCA Product
PDCA Product
PDCA Product
PDCA Product
Attached Power
Attached Power
Attached Power
Attached Power
Number
Number
Number
Number
Cord
Cord
Cord
Cord
A5800A Option 006 OLFLEX 190 (PN
600804), four-
conductor, 6-AWG
2
(16 mm
), 600- Volt,
60-Amp, 90- degree
C, UL, and CSA
approved, conforms
to CE directives
GN/YW ground wire.
A5800A Option 007 Five conductors, 10-
AWG (6 mm
450/475-Volt, 32-
Amp, <HAR>
European wire
cordage, GN/YW
ground wire.
Requirements
Requirements
Requirements
Requirements
Nominal Input Voltage (VAC rms)
Input Voltage Range (VAC rms)
Frequency Range (Hz)
Number of Phases
Maximum Input Current (A rms), 3-
Phase 5-wire
Maximum Input Current (A rms), 3-
Phase 4-wire
Maximum Inrush Current (A peak)
Circuit Breaker Rating (A),
3-Phase 5-wire
Circuit Breaker Rating (A),
3-Phase 4-wire
Power Factor Correction
Ground Leakage Current (mA)
The cooling system in Superdome was designed to maintain reliable operation of the system in the specified
environment. In addition, the system is designed to provide redundant cooling (i.e. N+1 fans and blowers) that
allows all of the cooling components to be "hot swapped."
Superdome was designed to operate in all data center environments with any traditional room cooling scheme (i.e.
raised floor environments) but in some cases where data centers have previously installed high power density systems,
DA - 11717
HP Integrity Superdome Servers: 16-way, 32-way,
HP Integrity Superdome Servers: 16-way, 32-way,
HP Integrity Superdome Servers: 16-way, 32-way,
HP Integrity Superdome Servers: 16-way, 32-way,
Attached Plug
Attached Plug
Attached Plug
Attached Plug
In Line Connector
In Line Connector
In Line Connector
In Line Connector
Mennekes ME 460P9
Mennekes ME 460C9 3-
3-phase, 4-wire, 60-
phase,
Amp, 250-Volt, UL-
4-wire, 60-amp, 250-Volt,
approved. Color
UL-approved. Color blue,
blue, IEC 309-1, IEC
IEC 309-1, IEC 309-1,
309-1, grounded at
grounded at 9:00 o'clock.
3:00 o'clock.
Mennekes ME
Mennekes ME 532C6 16 3-
2
),
532P6-14 3-phase,
phase, 5-wire, 32-Amp,
5-wire, 32-Amp,
450/475-Volt, VDE-
450/475-volt, VDE-
certified, color red, IEC
certified, color red,
309-1, IEC 309-2,
IEC 309-1, IEC 309-
grounded at 6:00 o'clock.
2, grounded at 6:00
o'clock.
Value
Value
Value
Value
200/208/220/230/240
200-240
50/60
3
20
40
90
25 A
45 A
0.95 minimum
>3.5 mA, with 6 BPSs installed
Worldwide — Version 1 — June 30, 2003
and 64-way
and 64-way
and 64-way
and 64-way
Customer Provided Part
Customer Provided Part
Customer Provided Part
Customer Provided Part
Panel Mount
Panel Mount
Panel Mount
Panel Mount
Receptacle
Receptacle
Receptacle
Receptacle
Mennekes ME 460R9 3
phase,
4-wire, 60-amp, 250-Volt,
UL-approved. Color blue,
IEC 309-1, IEC 309-1,
a
grounded at 9:00 o'clock.
Mennekes ME532R6 1276
3-phase, 5-wire, 32-Amp,
450/475-Volt, VDE-
certified, color red, IEC
309-1, IEC 309-2,
c
grounded at 6:00 o'clock.
Conditions/Comments
Conditions/Comments
Conditions/Comments
Conditions/Comments
Auto selecting. Measure at input
terminals
3-phase 5-wire with power cord;
3-phase 4-wire with power cord
3-phase source with a source voltage of
220 VAC measured phase to neutral
3-phase source with a source voltage of
either 208 VAC or 230 VAC measured
phase to phase
Per phase
Per phase
Warning label applied to the PDCA at
the AC Mains input
b
b
Page 17