Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) —208/230 Volts — Standard Efficiency
To Use
Heater
Tons
With
BAYHTRR105A
3
TSC036A1
BAYHTRR114A
BAYHTRR105A
BAYHTRR110A
4
TSC048A1
BAYHTRR114A
BAYHTRR118A
BAYHTRR105A
BAYHTRR110A
5
TSC060A1
BAYHTRR114A
BAYHTRR118A
BAYHTRR306A
3
TSC036A3
BAYHTRR318A
BAYHTRR306A
4
TSC048A3
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
5
TSC060A3
BAYHTRR318A
BAYHTRR323A
BAYHTRS309A
6
TSC072A3
BAYHTRS327A
BAYHTRS336A
BAYHTRS309A
TSC090A3
BAYHTRS327A
BAYHTRS336A
BAYHTRS309A
TSC092A3
BAYHTRS327A
BAYHTRS336A
BAYHTRT309A
TSC102A3
BAYHTRT327A
BAYHTRT336A
BAYHTRT318A
10
TSC120A3
BAYHTRT336A
BAYHTRT354A
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
52
Electrical
Data
Heater
1
Model No.
kW Rating
208/230 Volts Single Phase
3.8/5.0
BAYHTRR110A
7.5/10.0
10.4/13.8
3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6
3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6
208/230 Volts Three Phase
4.5/6.0
BAYHTRR312A
9.0/12.0
13.1/17.4
4.5/6.0
BAYHTRR312A
9.0/12.0
13.1/17.4
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
6.8/9.0
BAYHTRS318A
13.5/18.0
20.3/27.0
27.0/36.0
6.8/9.0
BAYHTRS318A
13.5/18.0
20.3/27.0
27.0/36.0
6.8/9.0
BAYHTRS318A
13.5/18.0
20.3/27.0
27.0/36.0
6.8/9.0
BAYHTRT318A
13.5/18.0
20.3/27.0
27.0/36.0
13.5/18.0
BAYHTRT327A
20.3/27.0
27.0/36.0
40.6/54.0
Standard Indoor Motor
Control
Max Fuse Size Or
Stages
MCA
Max Circuit Breaker
1
25.5/28.9
40/40
2
48.0/55.0
50/60
2
65.1/74.8
70/80
1
34.0/34.0
50/50
2
49.6/56.6
50/60
2
66.8/76.4
70/80
2
84.0/96.1
90/100
1
47.3/47.3
60/60
2
52.9/59.9
60/60
2
70.0/79.6
80/80
2
87.3/99.4
90/100
1
18.5/20.9
25/25
2
34.1/39.0
35/40
2
48.3/55.3
50/60
1
23.9/23.9
35/35
2
35.8/40.6
40/45
2
49.9/56.9
50/60
1
31.5/31.5
50/50
2
39.0/43.9
50/50
2
53.1/60.1
60/70
2
67.8/76.9
70/80
1
32.7/33.4
50/50
1
53.1/60.4
60/70
2
76.6/87.5
80/90
2
100.1/114.5
110/125
1
42.7/42.7
60/60
1
54.8/62.0
60/70
2
78.3/89.1
80/90
2
101.8/116.1
110/125
1
38.9/38.9
50/50
1
54.8/62.0
60/70
2
78.3/89.1
80/90
2
101.8/116.1
110/125
1
45.1/45.1
60/60
1
54.8/62.0
60/70
2
78.3/89.1
80/90
2
101.8/116.1
110/125
1
58.6/65.9
60/70
2
82.1/93.0
90/100
2
105.8/120.0
110/125
2
152.5/141.7
175/150
(Standard
Efficiency)
Oversize Indoor Motor
Max Fuse Size Or
2
MCA
Max Circuit Breaker
28.5/31.9
51.0/58.0
68.1/77.8
36.1/36.1
52.3/59.3
69.4/79.0
86.6/98.8
49.0/49.0
55.0/62.0
72.1/81.8
89.4/101.54
21.5/23.9
37.1/42.0
51.3/58.3
26.0/26.0
38.4/43.3
52.5/59.5
33.2/33.2
41.1/46.0
55.3/62.3
69.9/79.0
34.0/35.0
54.8/62.0
78.3/89.1
101.8/116.1
110/125
45.8/45.8
58.6/65.9
82.1/93.0
105.6/120.0
110/125
42.0/42.0
58.6/65.9
82.1/93.0
105.6/120.0
110/125
48.2/48.2
58.6/65.9
82.193.0
105.6/120.0
110/125
63.6/70.9
87.1/98.0
110.6/125.0
125/125
157.5/146.7
175/150
2
40/40
60/60
70/80
50/50
60/60
70/80
90/100
60/60
60/70
80/90
90/110
30/30
40/45
60/60
40/40
40/45
60/60
50/50
50/50
60/70
70/80
50/50
60/70
80/90
60/60
60/70
90/100
50/50
60/70
90/100
60/60
60/70
90/100
70/80
90/100