Trane Precedent RT-PRC005 User Manual page 50

Packaged cooling with electric heat rooftop units 3 - 10 tons - 60 hz
Table of Contents

Advertisement

Table ED-1 — Unit Wiring — Standard Efficiency
Unit
Tons
Model No.
TSC036A1
3
TSC036A3
TSC036A4
TSC036AW
TSC048A1
TSC048A3
4
TSC048A4
TSC048AW
TSC060A1
TSC060A3
5
TSC060A4
TSC060AW
TSC060AK
TSC072A3
6
TSC072A4
TSC072AW
TSC072AK
TSC090A3
TSC090A4
TSC090AW
TSC090AK
TSC092A3
TSC092A4
TSC092AW
TSC102A3
TSC102A4
TSC102AW
TSC102AK
TSC120A3
10
TSC120A4
TSC120AW
TSC120AK
NOTES:
1. HACR breaker per NEC.
2. Optional Belt Drive motor applies to 3-5 ton models only.
The standard motor for 6-10 ton models is belt drive.
50
Electrical
Data
Standard Indoor Fan Motor
Unit
Minimum Maximum Fuse
Operating
Circuit
Size Or Maximum
Voltage Range
Ampacity
Circuit Breaker
187-253
25.3
187-253
17 .9
414-506
9.2
517-633
7 .7
187-253
34.0
187-253
23.9
414-506
12.8
517-633
9.8
187-253
47 .3
187-253
31.5
414-506
16.0
517-633
12.2
342-418
19.6
187-253
32.7
414-506
17 .6
517-633
12.8
342-418
23.2
187-253
42.7
414-506
22.6
517-633
17 .6
342-418
28.4
187-253
38.9
414-506
20.5
517-633
15.5
187-253
45.1
414-506
24.0
517-633
19.5
342-418
32.6
187-253
52.6
414-506
26.9
517-633
21.8
342-418
32.6
(Standard
Efficiency)
Oversize Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size Or Maximum
1
Ampacity
Circuit Breaker
40
27 .7
40
25
20.3
30
15
10.4
15
15
8.3
15
50
36.1
50
35
26.0
40
20
14.4
20
15
10.6
15
60
49.0
60
50
33.2
50
25
16.3
25
15
12.8
20
30
50
34.0
50
25
18.2
25
20
13.6
20
35
60
45.8
60
35
24.1
35
25
18.8
25
40
29.9
45
50
42.0
50
25
22.0
25
20
16.7
20
60
48.2
60
30
25.5
35
25
20.7
25
40
35.6
45
60
56.6
60
35
28.9
35
25
23.5
30
40
35.6
45
Optional
Belt Drive Indoor Fan Motor
2
Minimum
Maximum Fuse
Circuit
Size or Maximum
1
1
Ampacity
Circuit Breaker
N/A
N/A
20.6
30
10.6
15
8.3
15
N/A
N/A
25.3
35
13.6
20
10.0
15
N/A
N/A
30.3
45
15.6
25
11.8
15
RT -PRC005-EN