Tripp Lite SMART2500XLHG Owner's Manual page 11

Intelligent, line-interactive, medical-grade ups system
Table of Contents

Advertisement

Available languages

Available languages

Guidance and Manufacturer's Declaration
Guidance and Manufacturer's Declaration—Electromagnetic Immunity
This Medical-Grade UPS is intended for use in the electromagnetic environment specified below. The
customer or the user of this Medical-Grade UPS should assure that it is used in such an environment.
Immunity Test
Electrostatic Discharge (ESD)
IEC 61000-4-2
Electrical Fast Transient/Burst
IEC 61000-4-3
Surge
IEC 61000-4-5
Voltage dips, short
interruptions and voltage
variations on power supply
input lines
IEC 61000-4-11
Power Frequency (50/60 Hz)
Magnetic Field
IEC 61000-4-B
Note: U
is the AC mains voltage prior to application of the test level.
T
Overcurrent Protection
The unit is equipped with 2 20A, branch-rated, circuit breakers.
Battery Pack
The unit comes with a 48VDC, rechargeable sealed lead-acid battery pack rated at 9 amp
hours. Your battery should last for several years. If needed, replacement battery packs for this
UPS are available through Tripp Lite, model number RBC48V-HGTWR.
12-10-307-93-3181.indb 11
IEC 60601 Test Level
+ / - 6kV contact
+ / - 8kV air
+ / - 2kV for power supply
lines
+ / - 1kV for input/output
lines
+ / - 1kV differential mode
+ / - 2kV common mode
<5% U
T
(>95% dip in U
) for .5 cycle
T
40% U
T
(60% dip in U
) for 5 cycles
T
70% U
T
(30% dip in U
) for 25 cycles
T
<5% U
T
(>95% dip in U
) for 5 seconds
T
3 A/m
11
Compliance
Electromagnetic
Level
Environment - Guidance
Complies
Floors should be wood,
concrete or ceramic tile. If
colors are covered with
synthetic material, the
relative humidity should be
at least 30%.
Complies
Mains power quality should
be that of a typical
commercial or hospital
environment.
Complies
Mains power quality should
be that of a typical
commercial or hospital
environment.
Complies
Mains power quality should
be that of a typical
commercial or hospital
environment.
Complies
Power frequency magnetic
fields should be at levels
characteristic of a typical
location in a typical
commercial or hospital
environment.
cont.
11/2/2012 9:27:49 AM