Nominal Input Voltage(s)
Supported
UPS input connection type
UPS input connection
description
Input circuit breaker
BATTERY
Full load runtime (minutes)
Half load runtime
(minutes)
Expandable battery
runtime
External battery pack
compatibility
DC system voltage (VDC)
Battery recharge rate
(included batteries)
Replacement battery
cartridge (internal UPS
battery replacement)
Battery Access
Battery replacement
description

VOLTAGE REGULATION

Voltage regulation
description
Overvoltage correction
Undervoltage correction
Severe undervoltage
correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
UPS AC suppression
response time
EMI / RFI AC noise
suppression
230V AC
C20 inlet
IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall
receptacles
20A
4 min. (2250w)
11 min. (1125w)
Extended runtime supported via optional external battery packs
BP48V24-2U
(limit 1);
BP48V60RT-3U
48
Less than 4.5 hours from 10% to 90%
RBC94-2U
Front panel battery access door
Hot-swappable, user replaceable batteries
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278
Input voltages between 244 and 278 are reduced by 12%
Input voltages between 182 and 206 are boosted by 12%
Input voltages between 158 and 182 are boosted by 24%
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure, overload and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation; Rear dip-switch for charger rate
adjustment
480
Instantaneous
Yes
(multi-pack compatible)