Elevated Operating Ambient; Reduced Air Flow; Mechanical Loading; Circuit Overloading - Wegener DVR396 Installation Manual

Digital video receiver
Table of Contents

Advertisement

Page 10
required if the room is cool (<75°F). For higher rack mounting densities, forced-air rack
ventilation is strongly recommended. Please note the average per-unit power dissipation of 45
watts (@ max LNB DC current loading) and plan accordingly.
Parameter
Input Rating
Operating Temperature Range
Operating Humidity
Maximum Operating Elevation
1.3.3

Elevated Operating Ambient

If equipment is installed in a closed or multi-unit rack assembly, the operating ambient of the
rack may be greater than the room ambient. Therefore, considerations should be given to the
TMRA, or Temperature inside the Mounting Rack, and not just inside the room.
1.3.4

Reduced Air Flow

Installation of the equipment in a rack should be such that the amount of airflow required for safe
operation of the equipment is not compromised.
1.3.5

Mechanical Loading

Mounting of equipment in a rack should be such that a hazardous condition is not achieved due
to uneven loading
1.3.6

Circuit Overloading

Consideration should be given to connection of the equipment to the supply circuit and the effect
that overloading of circuits could have on overcurrent protection and supply wiring. Appropriate
consideration of equipment nameplate ratings should be used when addressing this concern.
1.3.7

Reliable Earthing

Reliable earthing of rack-mounted equipment should be maintained. Particular attention should
be given to supply connections other than direct connection to the Branch (use of power strips).
DVR395/DVR396-002

Table 1. Equipment Specifications

Specification
115/230 VAC, 0.8/0.5A, 50/60Hz
5° - 40° C
Maximum relative humidity 80% for
temperatures up to 31° C, decreasing linearly
to 50% relative humidity at 40° C.
6560 Ft (2000M) above sea level
Page 10 of 30