Predefined heating curves (codes 112, 114, 116, 117)
A
60
6
5
4
50
3
40
1
2
30
20
-20
-15
-10
-5
0
A
9
10
11
60
8
50
7
40
30
20
-20
-15
-10
-5
0
Code function
Description
Predefined heating
0 = Personalised graph (see codes 118 to 121)
112
curves
1 to 12 = Pre-defined graphs (see above graphs)
114
ECO heating mode
Reduction offset for the installation's water temperature setting in heating mode.
116
117
Personalised heating curves (codes 118, 119, 120, 121)
A
60
4
50
40
1
30
20
10
0
-20
-15
-10
-5
0
Code function
Description
Minimum reference
Choose the minimum reference exterior temperature for the region where the
118
exterior temperature
heat pump is installed.
Exterior temperature
When the exterior temperature reaches the input value, heat pump stops.
from which the heat
119
Choose the exterior temperature from which the heat pump must stop in heating
pump stops in heating
mode.
mode
Minimum temperature
of water in the
Choose the minimum temperature of the water in the installation in heating
120
installation in heating
mode.
mode
Maximum temperature
of the water in the
Choose the maximum temperature of the water in the installation in heating
121
installation in heating
mode.
mode
122
Installer_manual_OEM_Vaillant_PROTO_3_GB - 06/11 - Vaillant
B
5
10
15
20
12
B
5
10
15
20
3
2
B
5
10
15
20
Setting codes 118 to 121 is necessary only if code 112 = 0.
Key
1
Heating graph n°1
2
Heating graph n°2
3
Heating graph n°3
4
Heating graph n°4
5
Heating graph n°5
6
Heating graph n°6
7
Heating graph n°7
8
Heating graph n°8 (factory setting)
9
Heating graph n°9
10 Heating graph n°10
11 Heating graph n°11
12 Heating graph n°12
A
Heating flow temperature (°C)
b
Exterior temperature (°C)
Not used
Not used
Key
1
Code 118
2
Code 119
3
Code 120
4
Code 121
A
Heating flow temperature (°C)
b
Exterior temperature (°C)
Not used
INSTALLATION
Setting
factory
Modifiable
setting
parameter
Min
Max
1
12
8
Yes
1°C
20°C
5°C
Yes
Setting
factory
Modifiable
setting
parameter
Min
Max
-20°C
10°C
-7°C
Yes
10°C
30°C
20°C
Yes
20°C
60°C
40°C
Yes
20°C
60°C
55°C
Yes
- 41 -