Flue Pipe; 100 Mm Standard Flue Pipe; Optional 125 Mm Flue Pipe; Termination Of The Flue Pipe - Vaillant ecoTEC exclusive SERIES Installation And Maintenance Instructions Manual

Gas wall boilers with condensing appliance technology
Hide thumbs Also See for ecoTEC exclusive SERIES:
Table of Contents

Advertisement

5 Installation
5.6

Flue pipe

d
Danger!
Vaillant appliances are only system-certified if
genuine Vaillant flue pipes are used. Only use
genuine Vaillant flue pipes. Malfunctions can
occur if you use other accessories. These may
result in damage and injury. You will find a list
of genuine flue pipes in the Vaillant installation
manual for flue pipes. The CE mark is valid only
if the appliance is operated with Vaillant flue
pipes.
5.6.1

100 mm standard flue pipe

Fig. 5.5 Item No. 303933
A 100 mm standard flue pipe (Item No. 303933) is avail-
able. Further information can be obtained from the in-
stallation instructions for the flue pipe. Extensions are
available to increase this length to a maximum of 8 m.
90° elbows and 45° elbows are also available to in-
crease the flexibility during installation.
Fig. 5.6 Item No. 303900
14

5.6.2 Optional 125 mm flue pipe

A concentric flue pipe having an outside diameter of
125 mm is available, which can be extended to a length
of up to 21 m. You can also get a vertical system. Fur-
ther information can be obtained from the installation
instructions for the flue pipe.
Fig. 5.7 Item No. 303209
Fig. 5.8 Item No. 303200
5.7

Termination of the flue pipe

The following information applies to both flue pipe sys-
tems.
a. The flue terminal must be located in such a position
that any flammable substances can be freely dissipat-
ed.
b. Water condensation (known as pluming) can also arise
at the terminal of the flue pipe. Installation sites
where these appearances may cause a problem should
be avoided.
c. If the flue terminal is less than 2 m above a balcony,
the ground or a flat roof that is accessible by persons,
a suitable protection guard should be fitted (manufac-
tured by Tower Flue Components, Tonbridge, TN9 1TB,
Model K3, plastic-coated).
ecoTEC exclusive installation and maintenance instructions / 0020017768_02