Overview Of The Settable Installation Parameters; Setting The Heating Partial Load; Setting The Pump Overrun Time; Setting The Maximum Flow Temperature - Vaillant ecoTEC exclusive SERIES Installation And Maintenance Instructions Manual

Gas wall boilers with condensing appliance technology
Hide thumbs Also See for ecoTEC exclusive SERIES:
Table of Contents

Advertisement

7.2

Overview of the settable installation parameters

The following parameters can be set to match the
appliance to the heating system and to suit the
customers requirements:
Display
Meaning
d.0
Heating partial load ecoTEC exclusive 832
d.1
Pump overrun time for heating operation
(starts after completion of heat demand)
d.2
Max. blocking time heating at 20°C feed
temperature
d.14
Pump speed target value
d.17
Heating flow/return regulation changeover 0 = flow, 1 = return
d.18
Pump mode (return flow)
d.26
Changeover option relay to electronic
d.71
Target value max. heating flow temperature 40 to 85 °C
d.84
Maintenance indicator: Number of hours
until the next maintenance
Table 7.1 Adjustable parameters
Note!
h
You can enter your settings in the end column
after setting the appliance-specific parameters.
h
Note!
The diagnosis points d.17, d.71 and d.84 are lo-
cated in the 2nd. diagnosis level, see Chapter
9.1.2
7.2.1

Setting the heating partial load

The units are set in the factory to a possible heat load
but not yet to the maximum value. Under diagnosis
point "d.0" you can set a value which corresponds to
the required output in the heating system in kW.
ecoTEC exclusive installation and maintenance instructions / 0020017768_02
Adapting the appliance to the heating system 7
Adjustable parameters
27 kW
ecoTEC exclusive 838
30 kW
2 - 60 min
2 - 60 min
Target value internal pump in % - possible set-
tings: Auto, 53, 60, 70, 85, 100 %
0 = return, 1 = nonstop, 2 = winter
1 = circulation pump
2 = Ext. pump (default)
3 = storage charging pump
4 = vapour extraction hood
5 = external throttle
6 = ext. fault signal (without maintenance dis-
play)
0 to 3000h and „-"
(300 corresponds to 3000 h, „-" = deactivated)

7.2.2 Setting the pump overrun time

The pump overrun time for the heating operation is set in
the factory to a value of 5 minutes. It can be set under
diagnosis point "1" within the range two minutes to
60 minutes. Under diagnosis point "d.18" you can set the
overrun behaviour of the pump to a different mode.
Overrun: After completion of the heat demand the heating
pump continues to run for the time set under "d.1".
Continuous: The internal heating pump is switched
on when the rotary knob for setting the heating feed
temperature is not in the left-hand stop position and the
heat demand is released by an external controller.
Winter: The internal heating pump is switched on when
the rotary knob for setting the heating feed temperature
is not in the left-hand stop position.
7.2.3

Setting the maximum flow temperature

The maximum feed temperature for the heating is set in
the factory to 75 °C. Under diagnosis point "d.71" it can
be set to between 40 und 85 °C.
Default
Appliance-specific
setting
setting
22 kW
27 kW
5 min
20 min
Auto
0
0
2
75 °C
-
27