Temperature Alarm Indications

When a Temperature Major Alarm is detected, the alarm card will illumi-
nate the TEMP LED and the MAJ LED. The alarm card will also activate
the MAJOR relay by connecting pin 2 to pin 6 on the Form-C output.

Power Supply Alarm Indications

When a Power Supply Minor Alarm is detected, the alarm card will illumi-
nate the PS LED and the MIN LED. The alarm card will also activate the
MINOR relay by connecting pin 5 to pin 9 on the Form-C output.
When a Power Supply Major Alarm is detected the alarm card will illumi-
nate the PS LED and the MAJ LED. The alarm card will also activate the
MAJOR relay by connecting pin 2 to pin 6 on the Form-C output.

System Alarms

The system alarms the Model 6103 can receive include:
• System Clear Alarm
• System Minor Alarm
• System Major Alarm
• System Critical Alarm
When a System Minor Alarm is transmitted, the alarm card will illuminate
the MINOR LED. The alarm card will also activate the MINOR relay by
connecting pin 5 to pin 9 on the Form-C output.
When either a System Major Alarm or a System Critical Alarm is trans-
mitted, the alarm card will illuminate the MAJOR LED. The alarm card
will also activate the MAJOR relay by connecting pin 2 to pin 6 on the
Form-C output.