Table PAF-1 — Enthalpy of Saturated AIR
Wet Bulb Temperature
Btu Per Lb.
40
15.23
41
15.70
42
16.17
43
16.66
44
17 .15
45
17.65
46
18.16
47
18.68
48
19.21
49
19.75
50
20.30
51
20.86
52
21.44
53
22.02
54
22.62
55
23.22
56
23.84
57
24.48
58
25.12
59
25.78
60
26.46
61
27 .15
62
27 .85
63
28.57
64
29.31
65
30.06
66
30.83
67
31.62
68
32.42
69
33.25
70
34.09
71
34.95
72
35.83
73
36.74
74
37 .66
75
38.61
28
Performance
Adjustment
Factors
Figure PAF-1 — Air Density Ratios
Air Density
Ratio (Density
at New
Air Density)
Condition/Std.
Table PAF-2 — Cooling Capacity Altitude Correction Factors
Sea Level
Cooling Capacity
Multiplier
1.00
KW Correction
Multiplier
(Compressors)
1.00
SHR Correction
Multiplier
1.00
Maximum
Condenser
Ambient
115 F
Note:
SHR = Sensible Heat Ratio
Table PAF-3 — Gas Heating Capacity Altitude Correction Factors
Sea Level
2001
To 2000
To 2500
Capacity
Multiplier
1.00
.92
Note:
Correction factors are per AGA Std 221.30 — 1964, Part VI, 6.12. Local codes may supersede.
Altitude/Temperature Correction
Rooftop Leaving Air Temperature (degrees F)
Altitude (Ft.)
1000
2000
3000
4000
0.99
0.99
0.98
0.97
1.01
1.02
1.03
1.04
.98
.95
.93
.91
114 F
113 F
112 F
111 F
Altitude (Ft.)
2501
3501
4501
To 3500
To 4500
To 5500
.88
.84
.80
5000
6000
7000
0.96
0.95
0.94
1.05
1.06
1.07
.89
.87
.85
110 F
109 F
108 F
5501
6501
To 6500
To 7500
.76
.72
RT -PRC010-EN