Bacnet Communications Interface For Chillers (Bci-C) - Trane CGAM Installation & Operation Manual

Air-cooled scroll chillers 20 - 130tons
Hide thumbs Also See for CGAM:
Table of Contents

Advertisement

Installation - Electrical

BACnet Communications Interface for Chillers (BCI-C)

The optional BACnet Communication Interface for Chillers
(BCI-C) is comprised of aTracer UC400 controller with
interface software. It is a non-programmable
communications module that allows the RTWD or RTUD
unit to communicate on a BACnet communications
network.
BACnet Data Points and Configuration
Property Definitions
The BCI-C device allows certain models ofTrane chillers
with CH530 controls to communicate with BACnet
systems and devices using BACnet MS/TP .This section
includes information about:
BACnet protocol implementation conformance
statement (PICS)
Object types: descriptions and configuration (refer to
Table 41, p.
79)
BACnet protocol: data link layers, device address
binding, networking options, and character sets
Object data points and configurations
BACnet Protocol Implementation
Conformance Statement (PICS)
Standardized Device Profile (Annex L)
Profile Description
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Building Controller (B-BC)
BACnet Operator Workstation (B-OWS)
BACnet Smart Actuator (B-SA)
BACnet Smart Sensor (B-SS)
78
Interoperability Building Blocks (Annex K)
Data Sharing-COV-B (DS-COV-B)
Data Sharing-ReadProperty-A (DS-RP-A)
Data Sharing-ReadProperty-B (DS-RP-B)
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing-WriteProperty-A (DS-WP-A)
Data Sharing-WriteProperty-B (DS-WP-B)
Data Sharing-WritePropertyMultiple-B (DS-WPM-B)
Alarm and Event Management Description
Alarm and Event-ACKI-B (AE-ACK-B)
Alarm and Event-Alarm Summary-B (AE-ASUM-B)
Alarm and Event-Enrollment Summary-B (AE-ESUM-
B)
Alarm and Event-Information-B (AE-INFO-B)
Alarm and Event-Notification Internal-B (AE-N-I-B)
Trending Description
Trending-Automated Trend Retrieval-B (T-ATR-B)
Trending-viewing and Modifying Trends Internal-B (T-
VMT-I-B)
Device Management Description
Supported
Device Management-Backup and Restore-B (DM-BR-
Profile
B)
Device Management-Device Communication Control-
B (DM-DCC-B)
ü
Device Management-Dynamic Device Binding-A (DM-
DDB-A)
Device Management-Dynamic Device Binding-B (DM-
DDB-B)
Device Management-Dynamic Object Binding-B (DM-
DOB-B)
Device Management-List Manipulation-B (DM-LM-B)
Device Management-Object Creation and Deletion-B
(DM-OCD-B)
Device Management-Private Transfer-A (DM-PT-A)
Device Management-Private Transfer-B (DM-PT-B)
Device Management-Reinitialize Device-B (DM-RD-B)
Device Management-TimeSynchronization-B (DM-TS-
B)
Segmentation Capability
Segmented Requests/ Window Size: 1
Segmented Responses/ Window Size: 1
Data Sharing Description
Segmentation Description
Supported
BIBB
ü
ü
ü
ü
ü
ü
Supported
BIBB
ü
ü
ü
ü
ü
Supported
BIBB
ü
ü
Supported
BIBB
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
Supported
Segment
ü
ü
CG-SVX17E-EN