Trane CGAM Installation & Operation Manual page 20

Air-cooled scroll chillers 20 - 130tons
Hide thumbs Also See for CGAM:
Table of Contents

Advertisement

Unit Dimensions/Weights
Figure 14. CGAM 60 and 70 ton - no options
Control panel
88.4 in
(2245 mm)
The number of fans shown does not represent
the number of fans installed.
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 15. CGAM 60 and 70 ton - service clearances and mounting locations
Service and Airflow
The number of fans shown does not represent
the number of fans installed.
Door
swing
47.2 in (1200 mm)
1
More clearance may be needed for airflow
depending on the installation.
20
Wire
connection
84.8 in
(2155 mm)
23.8 in
(603 mm)
125.8 in (3196 mm)
1
Clearance
39.4 in
39.4 in(1000 mm)
31.5 in
(800 mm)
Fan
Compressor
149.8 in (3804 mm)
Mounting Locations
Distance from edge to
middle of mounting hole
1.5 in (38 mm)
(1000 mm)
85.4 in
(2169 mm)
Control
panel side
19.4 in
79.7 in (2024 mm)
Total of six mounting locations.
14.4 in
(367 mm)
Water connections are even with unit end.
Hole dia
0.56 in (15 mm)
Chilled water
connection side
(493 mm)
129.8 in (3297 mm)
CG-SVX17E-EN
Chilled water
inlet
Chilled water
outlet
31.1 in
(790 mm)
7.9 in
(199 mm)