Partial Heat Recovery Freeze Protection

The heat recovery condenser is insulated and a factory-
installed heater is installed and will protect the heat
exchanger from freezing in ambient temperatures down to
-20°F (-29°C).
When the ambient temperature drops to approximately
39°F (3.9°C) the thermostat energizes the heaters.
Note: The inlet and outlet piping should be protected
against freezing by one of the following methods:
Install heat tape on all field-installed water piping.
OR
Add freeze inhibit fluid to the partial heat recovery
water loop.