Vinotemp Wine-Mate WM-2500SSHWC Installation, Operation & Care Manual

Vinotemp Wine-Mate WM-2500SSHWC Installation, Operation & Care Manual

Duct split cooling system

Advertisement

Quick Links

w
w
w
w
w
Duct Split Cooling System
Installation, Operation & Care Manual
WM-2500SSHWC WM-4500SSHWC
WM-6500SSHWC WM-8500SSHWC
w
w
w
w
R
e
a
d
a
n
d
s
a
R
e
a
d
a
n
d
s
a
.
w
i
n
e
m
a
t
e
.
c
o
m
w
.
w
i
n
e
m
a
t
e
.
c
o
m
w
.
v
i
n
o
t
e
m
p
.
c
o
m
w
.
v
i
n
o
t
e
m
p
.
c
o
m
v
e
t
h
e
s
e
i
n
s
t
r
v
e
t
h
e
s
e
i
n
s
t
r
u
c
t
i
o
n
s
u
c
t
i
o
n
s

Advertisement

Table of Contents
loading

Summary of Contents for Vinotemp Wine-Mate WM-2500SSHWC

  • Page 1 Duct Split Cooling System Installation, Operation & Care Manual WM-2500SSHWC WM-4500SSHWC WM-6500SSHWC WM-8500SSHWC...
  • Page 2: Important Safety Information

    Important Safety Information WARNING: • Do not use a ground fault interrupter (GFI). • A dedicated 20 AMP circuit for WM-2500SSHWC and 30 AMP for WM- 4500~8500SSHWC are required. - 1 -...
  • Page 3: Table Of Contents

    Table of Contents Cellar Construction.…………………………….……………..3 Features & Specifications…………………….….…………..4 Temperature & Humidity……….…………..………..……….6 Care Guide…………………………………………………….10 User’ Troubleshooting…….………………………………...11 Installer’s Instructions………….…..….……..…………….14 Electrical Wirings..…………….…..….……..………………24 Customer Support……………………………………………26 Warranty……………………………………………………….27 - 2 -...
  • Page 4: Cellar Construction

    Cellar Construction This is only a guide and shall be considered as minimum requirements. All interior walls and floors shall have a vapor barrier and a minimum of R13 insulation. All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation.
  • Page 5: Features & Specifications

    Features and Specifications • Wine-Mate duct split cooling systems WM-2500~8500SSHWC are designed and used to provide a cold temperature between 50~65 °F for a properly insulated wine cellar. • The wine cellar will maintain humidity range within 50~70% RH. • These temperature and humidity ranges like in natural caves are optimized for long term storage of wine.
  • Page 6 Cond Unit Btu/h Cellar Size Model No Refrigerant Evap Unit/ Evap Unit/ L”xW”xH”-S” L”xD”xH” (cu ft) Cond Unit Cond Unit WM-25SFCH WM-250SCU- 2500 115V-60HZ-0.8A WM-2500SSHWC 22.5x15.875 R134a 35/40 115V-60HZ-5.7A x14.375-11 24x18x18 WM-45SFCH WM-450SCU- 4500 115V-60HZ-1.8A WM-4500SSHWC 25.125x22.875 1000 R134a 45/60 115V-60HZ-6.9A...
  • Page 7: Temperature & Humidity

    Temperature and Humidity 1. Use of the controller Fig. 2 Temperature Controller 1) Keys SET: To display target set point; in programming mode it selects a parameter or confirm an operation. (DEF): To start a manual defrost. (UP): To see the maximum stored temperature; in programming mode it browses the parameter codes or increases the displayed value.
  • Page 8 4) Alarm Signals The alarm codes are described as follows. MESSAGE CAUSE FUNCTION Temperature probe faulty Compressor switching to Con and CoF Probe temperature ALU higher than the High temperature alarm setting temperature; Outputs unchanged Probe temperature ALL lower than the Low temperature alarm setting temperature;...
  • Page 9 5. How to calibrate the air temperature probe If the actual cellar temperature differs from the displaying temperature, set ot = actual cellar temperature minus displaying temperature. 6. How to adjust defrost cycle In case there is excessive frost, the parameters FnC = C-y, idF = 6 and MdF = 20 can be used to avoid defrost.
  • Page 10 3) Press up/down keys to scroll to the required parameter within 10 sec. 4) Press the “SET” key to display its value. 5) Use up/down keys to change its value within 10 sec. 6) Press “SET” to store the new value. 7) To exit: Press SET + or wait 15sec without pressing a key.
  • Page 11: Care Guide

    Care Guide In general, always unplug system or disconnect power while doing care. 1. Condenser Water Line Cleaning • To clear any sediment that may accumulate, the water regulating valve may be manually flushed. • Insert screwdrivers under both sides of the valve spring guide and lift upwards to flush.
  • Page 12: User' Troubleshooting

    User’s Troubleshooting This Troubleshooting Chart is not prepared to replace the training required for a professional refrigeration service person, not is it comprehensive. Complaint Possible Causes Response a. Power cord not plugged a. Check power cord 1. Unit not b. No power from supply b.
  • Page 13 high or not b. Cellar too large b. Check for excessive size c. Cellar ambient temperature too c. Check installation location cooling and high running d. Malfunctioning fans d. Check for evaporator fan continually e. Evaporator airflow e. Check for air restrictions, air short- circulation, grille directions Improper condenser cooling Check water flow...
  • Page 14 inside ducts b. Continually running not stopping b. raise temperature setting increase defrost cycle c. Too cold supply air c. Increase flow raise temperature setting a. Duct not insulated a. Check for insulation 13.Condensate b. High humidity b. Use dehumidifier outside c.
  • Page 15: Installer's Instructions

    WINE-MATE split system is shipped as components and is ready for use only after a certified refrigeration technician has properly installed the system. Proper installation is critical. Vinotemp can only warrant the quality of the components. The installation and proper operation of the system must be warranted by the installer.
  • Page 16 CAUTION: Liquid and suction line locations may differ from what are shown here, please check on the units for proper installation. Fig. 3 WM-25~85SFCH Evaporator Unit - 15 -...
  • Page 17 Fig. 4 WM-250~850SCU-WC Condensing Unit Fig. 5 Liquid Filter Fig. 6 Liquid Indicator - 16 -...
  • Page 18 Fig. 7 Temperature Controller (4.25”L X 3.75D X 4.25”H) 2. Evaporator Unit Installation 1) WM-25~85SFCH evaporator units can be installed outside a wine cellar. It shall not be exposed to temperatures higher than 85 °F. 2) Air supply shall be unobstructed minimum 12” for a direct blow installation; leave 2”...
  • Page 19 Fig. 9 Base Valve Operation Water Flow Water-in Water-out Water Pressure Model No Condensing Unit (75°F inlet, gal/min) Connection Connection Drop (PSI) WM-2500SSHWC WM-250SCU-WC 3/8” FPT 1/2" ODF SOLDER WM-4500SSHWC WM-450SCU-WC 3/8” FPT 1/2" ODF SOLDER WM-6500SSHWC WM-650SCU-WC 3/8” FPT 1/2"...
  • Page 20 4) If the air probe is installed in a return duct, the evaporator fans shall be running all the time. Meanwhile due to the temperature differential the temperature, air probe calibration should be used in order to maintain the proper wine cellar temperature. Checking Control Settings Suction pressure setting: Cut out=10 psig;...
  • Page 21 The line sizes and refrigerant charges are listed as follows. Equivalent Liquid Suction Insulated Recommended Model No Drain Line Line Set Line Line Duct Charge WM-2500SSHWC <= 75 FT 1/4" OD 3/8” OD 7/8” OD 8” R134a/19 OZ WM-4500SSHWC <= 75 FT 1/4" OD 1/2” OD 7/8” OD 8”...
  • Page 22 Fig. 11 Water Regulating Valve 2) It may use a fan speed control to adjust the air flow to achieve the specified CFM. The fan will run from the minimum speed to full speed with the control knob at the lowest and highest speed position. To adjust the minimum speed, turn control knob to the lowest speed position, then rotate the setting (located on the side or front) clockwise to decrease the minimum speed or counter- clockwise to increase the minimum speed.
  • Page 23 8) If the superheat is high, check the subcooling first to know if the refrigerant charge is sufficient. If the charge is not sufficient, add more refrigerant. If the charge is good, then increase the evaporator suction pressure by turning the hex nut (5/16”) clockwise.
  • Page 24 Low superheat and low subcooling evaporator iced Low suction pressure and low to normal head pressure Evaporator restricted High superheat and normal to high subcooling u. Low suction pressure and normal head pressure u. Expansion valve restricted High superheat and normal subcooling v.
  • Page 25: Electrical Wirings

    Electrical Wiring Diagrams CAUTION: • Hidden lines are the field wirings. • Use minimum 14 gauge wires for power lines. • A safety switch is always recommended for the condensing unit. Fig. 14 WM-2500~4500SSHWC Wiring Diagram - 24 -...
  • Page 26 Fig. 15 WM-6500~8500SSHWC Electrical Wiring Diagram - 25 -...
  • Page 27: Customer Support

    Customer Support If you need further assistance, please contact us at: Vinotemp International 17631 South Susana Road Rancho Dominguez, CA 90221 Tel: (310) 886-3332 Fax: (310) 886-3310 Email: info@vinotemp.com - 26 -...
  • Page 28: Warranty

    BTU/H. While every effort has been made to provide accurate guidelines, VINOTEMP can not warranty its units to cool a particular enclosure. In case of failure, VINOTEMP cooling units must be repaired by the factory or its authorized agent. Repairs or modifications made by anyone else will void the warranty.
  • Page 29 VINOTEMP will, at its discretion, repair or replace the unit and return it free of charge to the original retail customer. If the unit is found to be in good working order, or beyond the initial twelve month period, it will be returned freight collect.

Table of Contents