Installation of control fittings
(cont.)
Note
Install the electrodes for water level control and the water level limiter in
accordance with the electrode installation instructions.
Match or adjust the electrodes to the switching points listed in the table.
Upon request, the electrodes supplied by the boiler manufacturer can be
matched to the boiler at the factory.
Only install one electrode for limiting the water level into each connector.
However, water level regulation and limiter can be combined.
Ensure the electrodes of multi−boiler systems are not interchanged.
Multiple level electrode
for operating pressure up to 0.5 bar
*1
1.
2.
*1
For trimming the electrode, see page 16.
15