V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR
52 DEGREE
ANGULAR
ROTATION
2-5/16 (58.7)
MAXIMUM
TRAVEL
Fig. 3. 7616BR Damper Crank Arm can be attached to
actuator shaft to drive a damper when valve is open.

WIRING

WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.
Wiring must comply with all applicable electrical codes,
ordinances and regulations. Wiring to the actuator must be
NEC Class 1.
Connect the power supply to terminals 1 and 2 on the V4055
terminal strip. Refer to Fig. 4 for Auxiliary Switch connections
and Fig. 5 for Max Flow Limit Switch connections. For typical
system hookups, refer to Fig. 6 and to instructions packed with
the device used to control the valve.
When all wiring connections are complete, replace the actuator
faceplate.
CAUTION
Operation Hazard.
Improper wiring can cause improper and
dangerous operation.
Label all wires prior to disconnection when servicing
valves. Wiring errors can cause improper and
dangerous operation.
NOTE: Pipe sealant is required on the conduit threads of
actuators with NEMA 4 enclosures.
Adjust Auxiliary Switch (If Used)
The Auxiliary Switch is adjustable throughout the stroke of
the actuator. With the switch installed in the actuator, turn
the adjusting screw (see Fig. 2) clockwise
switch to operate earlier in the stroke or counter-
clockwise
to cause the switch to operate later in the
60-2309—13
7616BR
DAMPER
ARM
SHAFT
2-11/16 (68.3)
RADIUS
M7322
to cause the
stroke.
1
2
PROOF-OF-CLOSURE
SWITCH
AUXILIARY
SWITCH
2
3
1
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND
DISCONNECT MEANS AS REQUIRED.
2
SWITCH BETWEEN THESE TWO LEADS IS CLOSED WHEN
VALVE IS SHUT (DE-ENERGIZED).
3
SWITCH BETWEEN THESE TWO LEADS IS OPEN WHEN
VALVE IS SHUT (DE-ENERGIZED).
Fig. 4. External connections to the V4055 Actuator.
7800 SERIES
RELAY
L2
MODULE
9
FIELD WIRING
INTERNAL WIRING
Fig. 5. Connecting the Max Flow
Limit Switch to the actuator.
NOTE: The Proof-of-Closure Switch is not adjustable.
Adjust Max Flow Limit Switch (If
Used)
The Max Flow Limit Switch is adjustable throughout the stroke
of the actuator. With the switch installed in the actuator, turn
the adjusting screw clockwise
operate earlier in the stroke or counter-clockwise
cause the switch to operate later in the stroke.
6
L1
HOT
1
L2
C
C
NC
NC
NO
NO
2
3
PUMP
VALVE
1
2
3
4
PUMP
MOTOR
TRAVEL
ADJUSTABLE
LIMIT
NO
MAX
SWITCH
FLOW
LIMIT
NC
SWITCH
C
M12798
to cause the switch to
M7334
to