Rio Outputs Fields; Rio Deltas Fields; Configuring The Unit Ventilator (Uv); Configuring A Unit Ventilator Controller - Honeywell WebVision User Manual

Web-based building manager
Table of Contents

Advertisement

WEBVISION™
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1. Click the Output_pane button on the left pane to open
the Output Configuration page.
2. Enter information into available fields.
3. Click Commit to save the settings or Reset to revert to
the last saved settings.
4. Click Next to display the Delta Configuration page or
Back to display the Input Configuration page.

RIO Outputs fields

Table 51. RIO Digital Outputs.
Name
Point
Select up to eight digital outputs, DO1 to DO8, from
Type
the following types:
• DISCRETE1 through DISCRETE8
• FLOAT1_OPEN through FLOAT8_OPEN
• FLOAT1_CLOSE through FLOAT8_CLOSE
• MODULATE1 through MODULATE8
The following additional parameters are also
available for configuration:
• Speed for Floating DOs
• PWM settings for Modulated DOs
For floating outputs, a corresponding float close
should be available for a float open and vice versa.
If not, the wizard gives an error message while you
try to save the configuration.
RIO Deltas
Use Table 52 to configure the RIO Deltas.
Purpose
Delta is an adjustable threshold that allows the user to
determine, on a per-sensor basis, what change in value is
required before the sensor is updated. All Excel 10 controllers
have a guaranteed periodic update time of 55 seconds, which
requires that all sensors report any change every update
period. The delta for each sensor is used to reduce LonWorks
Bus traffic by reducing the amount of updates on a sensor that
are constantly or quickly changing. View or modify Deltas
(change thresholds) for sensors.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1. Click the Deltas_pane button on the left pane to open
the RIO's Delta Configuration page.
2. Enter information into available fields.
3. Click Commit to save the settings or Reset to revert to
the last saved settings.
95-7769—01
Definition
4. If sensors are being used for display only, then they can
have a larger value for the delta and rely on the
guaranteed periodic update to update the sensor every
55 seconds regardless on the amount of change.
5. If the sensor is bound to another Excel 10 controller,
configure a smaller delta so that the control algorithm
does not see large changes in value.
6. The default value of 0 sends an update every 2
seconds.
7. Click Back to display the RIO's Input Configuration
page.

RIO Deltas fields

Table 52. RIO Deltas.
Name
Delta T1
Degrees Farheinheit (°F)
Delta T2
Degrees Farheinheit (°F)
Delta T3
Degrees Farheinheit (°F)
Delta T4
Degrees Farheinheit (°F)
Delta H
Percentage
Delta P
Inches H
Delta V
Volts
Delta C
Milliamperes
Delta CO
CO
2

Configuring the Unit Ventilator (UV)

The W7753A is the Unit Ventilator Controller in the Excel 10
product line family. The Unit Ventilator is a LonMark compliant
device to monitor/control HVAC equipment, lighting, and other
miscellaneous loads in a distributed network.
Refer to Excel 10 W7753A Unit Ventilator Controller
Specification Data (form 74-2962) or Excel 10 W7753A Unit
Ventilator Controller Installation Instructions (form 95-7520)
for more information. This literature is available on
customer.honeywell.com. Try the following link:
http://customer.honeywell.com/request.cfm?form=xx-xxxx
Navigating to Unit Ventilator Pages
Go to the Devices tab. Expand the list of devices on the left
pane (listed under WebVision). Select a device to view its
properties.

Configuring a Unit Ventilator Controller

The options for configuring a Unit Ventilator Controller are as
follows:
• Outputs
• Inputs
• Equipment Control
• Economizer
• H/C Stages
• Zone Options
• Miscellaneous
• PID
• Wiring Assignment
• Wiring Diagram
74
Definition
O
2
level
2