W7763C/D/E Chilled Ceiling Controller (Chc); Chc Point Details; Appendix B – Device Point Tables - Honeywell WebVision User Manual

Web-based building manager
Table of Contents

Advertisement

WEBVISION™
APPENDIX B – DEVICE POINT TABLES
This appendix provides a table for the points detail and a table
for the application of points of the following controllers and
devices:
• W7763C/D/E Chilled Ceiling Controller (CHC) .. page 106
• Constant Volume Air Handling Unit Controller
(CVAHU) ..............................................................page 114
• Fan Coil Unit Controller (FCU) ........................... page 122
• Hydronic Controller (HYD) ................................. page 129
• Excel 10 Remote Input/Output Device (RIO) ..... page 136
• Vacon NX Frequency Converter (NXVFD) ......... page 138
• T7350 Thermostat (T7350) ................................ page 138
• Unit Ventilator (UV) ............................................ page 138
• Excel 10 VAV II Controller (VAV II) ...................... page 145
• XL15C Plant Controller (XL15C) ......................... page 155
W7763C/D/E Chilled Ceiling
Controller (CHC)
Table 74 provides the CHC points detail and Table 75 on
page 107 provides the CHC application of points.
Point Name
Occupied Cool
Standby Cool
Unoccupied Cool
Occupied Heat
Standby Heat
Unoccupied Heat
Current State
Next State
Time To Next State
DLC Shed
Out Of Limits
Open Circuit
Out Of Service
Mechanical Fault
Feedback Failure
Over Range
Under Range
Electrical Fault
Unable To Measure
Command Failure
Self Test Failed
Application Mode
Fan Speed
Manual Mode
Manual Occupancy
Temporary Setpoint
Effective Setpoint
Alarm Type
95-7769—01
Table 74. CHC Point Details.
Network Variable
nciSetPnts
nciSetPnts
nciSetPnts
nciSetPnts
nciSetPnts
nciSetPnts
nviTodEvent
nviTodEvent
nviTodEvent
nviDlcShed
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nvoStatus
nviApplicMode
nviFanSpeedCmd
nviRequest
nviManOccCmd
nviSetPoint
nvoChcStatus
nvoChcStatus
106
Field Name
occupiedCool
standbyCool
unoccupiedCool
occupiedHeat
standbyHeat
unoccupiedHeat
currentState
nextState
timeToNextState
DlcShed
outOfLimits
openCircuit
outOfService
mechanicalFault
feedbackFailure
overRange
underRange
electricalFault
unableToMeasure
commFailure
failSelfTest
hvacMode
objectRequest
occupancy
tempP
activeSetPt
alarmType
Point Type
NumericWritable
NumericWritable
NumericWritable
NumericWritable
NumericWritable
NumericWritable
EnumWritable
EnumWritable
NumericWritable
EnumWritable
BooleanPoint
BooleanPoint
BooleanPoint
BooleanPoint
BooleanPoint
BooleanPoint
BooleanPoint
BooleanPoint
BooleanPoint
BooleanPoint
BooleanPoint
EnumWritable
SNVTSwitch
EnumWritable
EnumWritable
NumericWritable
NumericPoint
EnumPoint

Hide quick links:

Advertisement

Table of Contents
loading