Honeywell WebVision User Manual page 153

Web-based building manager
Table of Contents

Advertisement

Point Name
Adjust Input / Actual Value 2
Clear Counter
Drive Speed Setpoint
Free Analog / Input Actual Value 1
Reset Fault
Torque Reference / Reference for PID
AC Fault Code
Fault Active
DC Link Voltage
Drive Current
Drive Energy
Drive Power
Ready
Running
Drive Speed
Active Fault Code
Table 89. NXVFD Application of Points.
Graphics Alarms Trends
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
153
Commandable
Internal Use
X
X
X
X
X
X
WEBVISION™
Valid Values
Units=%
Precision=1
Min.=-163.8
Max=163.8
Units=%
Precision=1
Min=0.0
Max=100.0
Units=%
Precision=1
Min=0.0
Max=100.0
Units=%
Precision=1
Min.=-163.8
Max=163.8
Units=%
Precision=1
Min=0.0
Max=100.0
Units=%
Precision=1
Min.=-163.8
Max=163.8
Units=%
Precision=1
Min.=-163.8
Max=163.8
True or False
Units=%
Precision=1
Min=-163.8
Max=163.8
Units=A
Precision=1
Min=-3276.8
Max=3276.7
Units=kW/hr
Precision=0
Min=0.0
Max=65535.0
Units=kW
Precision=1
Min=0.0
Max=6553.5
True or False
True or False
Units=%
Precision=1
Min=-163.8
Max=163.8
Units=null
Precision=0
Min=0.0
Max=65535.0
95-7769—01