Honeywell WebVision User Manual page 116

Web-based building manager
Table of Contents

Advertisement

WEBVISION™
Point Name
Unoccupied Cool (Setpoint)
Occupied Heat (Setpoint)
Standby Heat (Setpoint)
Unoccupied Heat (Setpoint)
Current State
Next State
Time To Next State
DLC Shed
Air Flow Loss
Coil Freeze State
Dirty Filter
Frost Protect Alarm
Indoor Air Quality Override
Input Nv Fail
Invalid Setpoint
Low Limit Economizer Close
Node Disabled
Sensor Failure
95-7769—01
Table 77. CVAHU Application of Points. (Continued)
Graphics Alarms Trends Commandable Internal Use
116
Valid Values
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
X
Default
Occupied
Unoccupied
Bypass
Standby
X
Default
Occupied
Unoccupied
Bypass
Standby
X
Units=min
Precision=0
Min=0.0
Max=65535.0
X
dlNoDlcShed
dlMinDlcShed
X
False
True
X
False or True
X
False or True
X
False or True
X
False or True
X
False or True
X
False or True
X
False or True
X
False or True
X
False or True