WEBVISION™
Excel 10 Remote Input/Output
Device (RIO)
Table 82 provides the RIO points detail and Table 83 on
page 136 provides the RIO application of points.
Point name
Communication Failed
Node Disabled
Sensor Failed
Manual Mode
Analog In 1
Analog In 2
Analog In 3
Analog In 4
Analog In 5
Analog In 6
Digital In 1
Digital In 2
Digital In 3
Digital In 4
Digital Out 1
Digital Out 2
Digital Out 3
Digital Out 4
Digital Out 5
Digital Out 6
Digital Out 7
Digital Out 8
Mode
Point Name
Communication Failed
Node Disabled
Sensor Failed
Manual Mode
Analog In 1
Analog In 2
95-7769—01
Table 82. RIO Point Details.
Network Variable
nvoAlarmStatus
nvoAlarmStatus
nvoAlarmStatus
nviManualMode
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
nvorioIO
Table 83. RIO Application of Points.
Graphics
Alarms
Trends
X
X
X
X
X
X
X
X
X
CommFail
NodeDisable
SensorFail
manMode
ai1
ai2
ai3
ai4
ai5
ai6
di1
di2
di3
di4
d01
d02
d03
d04
d05
d06
d07
d08
mode
Commandable
X
X
X
X
136
Field
Point Type
EnumPoint
EnumPoint
EnumPoint
EnumWritable
NumericPoint
NumericPoint
NumericPoint
NumericPoint
NumericPoint
NumericPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
EnumPoint
Internal Use
Valid Values
False or True
False or True
False or True
Enable
Disable
Manual
Suppress Alarms
Unsuppress Alarms
Units=ºF
Precision=1
Min=-256.0
Max=256.0
Units=ºF
Precision=1
Min=-256.0
Max=256.0