INSTALLATION
BOILER ROOM
Important
Keep vents free at all times.
Do not store inflammable products in the boiler room.
Do not store corrosive products near the boiler, such as paints,
solvents, chlorine, salt, soap and other cleaning products.
If you smell gas, do not switch on the light or light a flame. Turn off
the mains gas tap at the meter and inform the appropriate
services immediately.
Access
The boiler room must be large enough to allow good access to the
boiler. The following minimum distances are required around the boiler:
- front
500 mm
- side
100 mm
- behind
150 mm
- above
700 mm
Ventilation
The boiler room must be fitted with top and bottom vents sized
according to the table below or to current regulations.
The table below gives an example conforming to the Belgian standards.
Ventilation
60 N
Min. fresh air
requirement
m
/h
126
3
Bottom
dm
2
2.11
Top
dm
2
2.0
Other countries should refer to their own standards.
Base
The base on which the boiler rests must be made of non-combustible
materials.
8
70 N
100 N
150
Jumbo
126
194
278
2.11
3.20
4.8
2.0
2.0
2.0
CHIMNEY CONNECTIONS
IMPORTANT
Boilers must be installed by an approved heating
engineer, in accordance with the prevailing local
standards and regulations.
Flue size should not be less then the outlet size of the
boiler.
Chimney connection type: B23
The boiler is connected to the chimney by a metal pipe rising at an
angle from the boiler to the chimney.
A flue disconnection piece is required.
This must be easy to remove to give access to the flue pipes when
servicing the boiler.
A. Top vent
B. Bottom vent
C. Draught regulator
D. Inspection window
E. Height of lined chimney
F. Chimney diameter
A
B
Chimney
60 N
minimum flue diameter
E = 5 m Ø F min. mm
189
E = 10 m Ø F min. mm
159
E = 15 m Ø F min. mm
150
Note:
Regulations vary from country to country therefore
the table above is intended only as a guide.
Due to the high efficiency of our boilers, the flue gasses
exit at low temperature. Accordingly, there is risk that
the flue gasses could condense, which could damage
the chimney. In order to avoid this risk, it is strongly
recommended that the chimney be lined.
F
C
D
70 N
100 N
150
Jumbo
189
234
286
159
178
250
150
150
250

Advertisement

loading

Summary of Contents for ACV 60 N

  • Page 1 B. Bottom vent C. Draught regulator The table below gives an example conforming to the Belgian standards. D. Inspection window E. Height of lined chimney F. Chimney diameter Ventilation 60 N 70 N 100 N Jumbo Min. fresh air requirement Bottom 2.11...
  • Page 2 INSTALLATION Balanced flue boiler connection type: C • C13: concentric horizontal connection • C33: concentric vetical connection • C53: parallel chimney connection • C63: concentric vertical connection without terminal (only in Germany and Luxembourg). Maximum length concentric : 6 metres Maximum length parallel : 12 metres Note: a 90 degree bend = 1 metre equivalent length A condensation drain outlet must be fitted close to the boiler to prevent condensation products from...
  • Page 3: Hot Water Connections

    If the mains water pressure is greater than 6 bar, a pressure reducing valve must be fitted. Expansion relief valve The tank expansion relief valve must be ACV approved and calibrated to a maximum of 7 bar. The valve discharge must be connected to the drain.
  • Page 4: Heating Connection

    INSTALLATION HEATING CONNECTION OIL SUPPLY CONNECTIONS - ACV BM BURNERS The HeatMaster has two connections at the rear that can be used to (If another make of buner is fitted please refer to that manufacturers technical connect a central heating circuit. Connecting a heating system may manual) reduce the domestic hot water performance.
  • Page 5: Electrical Connections

    Thermal reset high limit thermostat 95 °C Control thermostat 230 V servicing socket (only HM 150 Jumbo) Relay (only HM 150 Jumbo) Electrical connection HeatMaster 60 N, 70 N and 100 N N T1 T2 S3 B4 Blue N T1 T2 S3 B4 Black Brown...
  • Page 6 INSTALLATION Electrical connection HeatMaster 150 Jumbo Blue Pink Black Brown Violet Grey White Green Yellow Orange Y/Gr. Yellow / Green 95 C 10 - 100 C 103 C Y/Gr Y/Gr 6,3 A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 N T1 T2 S3 Y/Gr 220/240V...