In this way, you can add your own values to the list of options, and assign
any IP addresses:
For this purpose, you need a notebook or PC with an Ethernet connection to the
device. The notebook must already be in the desired IP subnet.
1. Open a CMD shell on the notebook.
2. Press the button until the list of options is displayed (operating level 2, IP
address flashes, only in this status can new values be added).
3. Now trigger a ping on the notebook with at least 4 attempts to the desired IP
address (e.g. ping –n 5 192.168.1.43).
4. The ping is not answered by the device, but the destination address is added
to the list of options, and can be accepted by a long button press.
8.2.3

Readout versions

The relevant software versions can be readout by one-button operation:
11:46:48
Mo, 4. Oct. 2010
IP address
192.168.001.010
Figure 8-10 Readout versions
The following versions can be readout:
Firmware version TC100
Core version TC400
Core version U300
Processor version
Siemens AG 2010 All Rights Reserved
®
SICLOCK
TC100 Operating Instructions
Parameter assignment and operation of the device
->GPS1
->
-->
Version
->
Firmware 1.53467
8-7