Siclock Gpsdec - Siemens SICLOCK TC100 Operating Instructions Manual

Plant central clock
Table of Contents

Advertisement

6.3.3

SICLOCK GPSDEC

(SICLOCK GPSDEC has been discontinued, please use SICLOCK GPS1000)
A SICLOCK GPSDEC decoder is connected as shown in Figure 6-5.
Figure 6-5 Connection of the radio clock SICLOCK GPSDEC to RADIO CLOCK 1
Caution
A SICLOCK GPSDEC may only be operated as an active radio clock.
Operation as a passive radio clock leads to the destruction of the
SICLOCK GPSDEC.
Table 6-2
Time difference from GMT
Daylight saving time change
X1.5-8 (DCF77TTY)
Functional check
The "RADIO CLOCK" LED on the front panel must flash at about 1Hz when the
GPSDEC is received correctly.
The parameter /Inputs/Input 1/Status (0.20.02) must change to "GPS" or "DCF77"
after about three minutes reception.
Siemens AG 2010 All Rights Reserved
®
SICLOCK
TC100 Operating Instructions
Recommended assignment of parameters to the GPSDEC decoder for
synchronizing a SICLOCK TC100
Parameter
Setting
00:00
„none"
„DCF without ZZB"
Connection
6-3