Advertisement

(5) With the vacuum pump still running, close the "Lo"
knob of the manifold valve. Then stop the vacuum
pump.
(6) With the accessory hex wrench, turn the valve
stem on the narrow tube service valve counter-
clockwise by 90 degrees (1/4 turn) for 10 seconds,
and then turn the stem clockwise to close it again.
(Fig. 53)
CAUTION
(7) Leak test all joints at the tubing (both indoor and
outdoors) with liquid soap. Bubbles indicate a leak.
Be sure to wipe off the soap with a clean cloth.
(8) With the hex wrench, turn the wide tube service
valve stem counter-clockwise to fully open the
valve.
(9) Turn the narrow tube service valve stem counter-
clockwise to fully open the valve.
(10) Loosen the vacuum hose connected to the wide
tube service port slightly to release the pressure.
Then, remove the hose.
(11) Replace the bonnet and flare nut on the wide tube
service port and fasten the flare nut securely with
an adjustable wrench or box wrench. Next, mount
the valve cap and tighten it with a torque wrench
(the cap needs to be tightened with the torque of
170 lbs.
in. (200 kg
important to prevent gas from leaking from the
system.
(12) Test run the air conditioner. (See next page.)
(13) While the air conditioner is running, apply liquid
soap to check for any gas leaks around the ser-
vice valves or caps.
(14) If there is no leakage, stop the air conditioner.
(15) Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and
the air conditioner is ready for actual operation.
Be sure to completely insert
the hex wrench before
attempting to turn the valve.
cm)). This process is very
90 (1/4 turn)
Vacuum hose to manifold valve
19
Narrow tube
Hex wrench
Wide tube
Valve cap
Fig. 53