Battery Specifications - HP R6000 series User Manual

Uninterruptible power system
Table of Contents

Advertisement

Table C-3: Output Specifications
Output Voltage
Utility Voltage (VAC)
Source of Utility Power
Utility power (normal range)
Utility power (extended range)
Battery power
Additional Features
On-line efficiency
Voltage wave shape while on battery
Surge suppression
Noise filtering

Battery Specifications

Table C-4: Battery Specifications
Feature
Type
Voltage
Charging
HP Uninterruptible Power System R6000 Models User Guide
continued
Nominal Output Voltage
200
208
220
230
240
Source
Feature
Specification
Sealed lead-acid, maintenance-free
Internal batteries 12 VDC each, 360 VDC total
24 hours to full charge
4 hours to 90% capacity at default nominal utility voltage and no load
(VAC)
200
208
220
230
240
Regulation
±10% of nominal output voltage (within the guidelines of
the Computer Business Equipment Manufacturers
Association)
+10% to -15% of nominal output voltage and/or +5/-3%
frequency (within the guidelines of the Computer
Business Equipment Manufacturers Association)
±5% of nominal output voltage
Specification
96%
Sinusoidal with less than 3% THD at linear load
High energy 6500 A peak (meets the requirements of
ANSI C62.41 Category B (formerly IEEE 587))
The input noise suppression is comprised of Normal
Mode Filtering, Common Mode Filtering, or a combination
of both.
Specifications
Nominal Output Voltage on
Battery (VAC)
204
204
230
230
230
C-3