Table 5-1: Responding to Audible Alarms
Audible Alarm Group
Caution
HP Uninterruptible Power System R6000 Models User Guide
continued
Audible Alarm Sound
A beep sounds every five
seconds.
Cause
The UPS is on battery
power.
The load is greater than
105%, and the manual
Bypass switch is in the
Bypass position.
An ambient over
temperature condition
occurs.
A button is being held
after the action is
completed.
The UPS performs a
self-test and detects a
memory location error.
A site-wiring fault occurs.
(Only if the site wiring
option is enabled.)
A self-test fails and is
indicated on the LCD
display.
The charger fails.
A fan fails.
The UPS is unable to
charge the batteries.
Troubleshooting
Action
Prepare for a UPS
shutdown.
Check the manual Bypass
switch on the rear of the
UPS. Turn it to the Normal
position. Reduce the load.
Verify that the air intake is
not blocked and the ambient
room temperature is correct.
If the problem still exists,
contact an authorized
service provider.
Let go of the button. Make
sure the button moves
freely, or is not lodged.
Turn off the UPS and call an
authorized service provider.
Use the front panel controls
and LCD display to examine
information on the warning.
If necessary, contact a
licensed electrician to check
the input wiring, or contact
an authorized service
provider.
Turn off the AC mains, wait
until the UPS shuts down,
then turn the breaker back
on and run a self-test. If the
self-test fails again, contact
an authorized service
provider.
Contact an authorized
service provider.
Contact an authorized
service provider.
Check battery connections
and make sure the battery
breaker is in the on position.
Run the UPS for 24 hours. If
the condition does not clear,
contact an authorized
service provider.
5-3