TABLE 4 — ALLOWABLE AMPACITIES OF INSULATED CONDUCTORS RATED 0-2000 VOLTS, 60° TO 90° C (140° TO 194° F).
NOT MORE THAN THREE CONDUCTORS IN RACEWAY OR CABLE OR EARTH (DIRECTLY BURIED), BASED ON
AMBIENT TEMPERATURE OF 30° C (86° F) (REFERENCE NEC TABLE 310-16)
SIZE
60° C
(140° F)
TYPES
TW¥, UF¥
AWG
kcmil
18
—
16
—
14
20¥
12
25¥
10
30
8
40
6
55
4
70
3
85
2
95
1
110
1/0
125
2/0
145
3/0
165
4/0
195
250
215
300
24
350
260
400
280
500
320
600
355
700
385
750
400
800
410
900
435
1000
455
1250
495
1500
520
1750
545
2000
560
¥ Unless otherwise specifically permitted in the NEC, the over current protection for conductor types marked with an ¥ shall not exceed 15 amperes for No.
14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum
after any correction factors for ambient temperature and number of conductors have been applied.