Step 9 Wiring The Fireplace - Heat & Glo 6000TR-OAK Owner's Manual

Installation and operation
Table of Contents

Advertisement

3/16" PIGGYBACK CONNECTOR
THERMOCOUPLE
Figure 35. Standing Pilot Ignition Wiring Diagram
Step 9. Wiring the Fireplace
NOTE: Electrical wiring must be installed by a licensed
electrician.
CAUTION: DISCONNECT REMOTE CONTROLS IF AB-
SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE-
VENT ACCIDENTAL FIREPLACE OPERATION.
For Standing Pilot Ignition Wiring
Appliance Requirements
• This appliance DOES NOT require 110-120 VAC to operate.
WARNING: DO NOT CONNECT 110-120 VAC
!
TO THE GAS CONTROL VALVE OR THE AP-
PLIANCE WILL MALFUNCTION AND THE
VALVE WILL BE DESTROYED.
BLK
BLK
BLK
TEMPERATURE
SENSOR SWITCH
Figure 36. Fan Wiring Diagram
30
GAS VALUE
RED T1
VARIABLE SPEED CONTROL
BLK
JUNCTION BOX
BLK
BLK
BLK
GROUND
GRN
BLK
110-120 VAC
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06
BLACK S2
ON
OFF
ON/OFF
WHITE T2
SWITCH
THERMOPILE
BLACK S1
Optional Accessories
Optional fan and remote control kits require that 110-120
VAC be wired to the factory installed junction box before
the fireplace is permanently installed.
Wall Switch
Position the wall switch in the desired position on a wall.
Run a maximum of 25 feet (7.8 m) or less length of 18
A.W.G. minimum wire and connect it to the fireplace ON/
OFF switch pigtails.
WARNING: DO NOT CONNECT 110-120 VAC
!
TO THE WALL SWITCH OR THE CONTROL
VALVE WILL BE DESTROYED.
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-
TION WHEN SERVICING CONTROLS. WIRING ERRORS
CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
VERIFY PROPER OPERATION AFTER SERVICING.
NOTE: IF ANY OF THE ORIGINAL WIRE
AS SUPPLIED WITH THE APPLIANCE
MUST BE REPLACED, IT MUST BE
REPLACED WITH TYPE 105 C RATED WIRE.
BLOWER RECEPTACLE
BLK
WHT
WHT
WHT
BLOWER
REMOTE SWITCH
PIGTAIL
OPTIONAL WALL SWITCH,
THERMOSTAT OR REMOTE
O
BLOWER
SENSOR
SWITCH
"FAN"
RECEPTACLE
SPEED
CONTROL