VENTING WITH ONE (1) 90° ELBOW
V
1' MIN. (305mm)
2' MIN. (610mm)
3' MIN. (914mm)
4' MIN. (1.22m)
V+H=40' MAX. (12.4m)
NOTE: On vertical venting configurations, where
the vertical component is over 10 feet, install
the flue restrictor included in the manual bag
assembly to improve flame appearance.
Figure 12. Venting with One 90° Elbow
VENTING WITH ONE (1) 90° ELBOW
V (FT.)
1' MIN. (305mm)
2' MIN. (610mm)
3' MIN. (914mm)
4' MIN. (1.22m)
V+H= 40' MAX. (12.4MM) H = 20' MAX. (6.2m)
H
Figure 13. Venting with One 90° Elbow
18
H
2' MAX. (610mm)
4' MAX. (1.22m)
6' MAX. (1.86m)
8' MAX. (2.4m)
H = 8' MAX. (2.4m)
H (FT.)
5' MAX. (1.52m)
10' MAX. (3.1m)
15' MAX. (4.65m)
20' MAX. (6.2m)
V
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06
V
H
NOTE: For corner installations: A 6-inch (152mm)
section of straight pipe may need to be attached to
the fireplace before a 90
pipe to clear the top standoffs.
NOTE: If a 90
elbow is first attached to the unit,
o
the maximum horizontal run is 3-feet (914mm).
H
elbow, to allow the vent
o
V