Heat Controller HSS Series Installation, Operation & Maintenance Instructions Manual page 33

Hss series split system, 11/2 to 5 tons hts series split system, two stage, 2-5 tons
Table of Contents

Advertisement

CXM Controls
CXM Control Start-up Operation
The control will not operate until all inputs and safety controls
are checked for normal conditions. The compressor will have a
5 minute anti-short cycle delay at power-up. The first time after
power-up that there is a call for compressor, the compressor will
follow a 5 to 80 second random start delay. After the random
start delay and anti-short cycle delay, the compressor relay will
be energized. On all subsequent compressor calls, the random
start delay is omitted.
Table 9b: Unit Operation
T-stat signal
G
G, Y or Y1
G, Y1, Y2
G, Y1, Y2, W
G, W
G, Y or Y1, O
G, Y1, Y2, O
1
Stage 1 = 1st stage compressor, 1st stage fan operation
Stage 2 = 2nd stage compressor, 2nd stage fan operation
Stage 3 = 2nd stage compressor, auxiliary electric heat, 2nd
or 3rd stage fan operation (depending on fan settings)
2
Stage 1 = 1st stage compressor, 1st stage fan operation, reversing valve
Stage 2 = 2nd stage compressor, 2nd stage fan operation, reversing valve
3
Stage 1 = compressor, 1st stage fan operation
Stage 2 = compressor, 2nd stage fan operation
Stage 3 = compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings)
4
Stage 1 = compressor, 1st stage fan operation, reversing valve
Stage 2 = compressor, 2nd stage fan operation, reversing valve
5
Stage 1 = compressor, fan
Stage 2 = compressor, auxiliary electric heat, fan
6
Cooling = compressor, fan, reversing valve
T h e Q u a l i t y L e a d e r i n C o n d i t i o n i n g A i r
HTS
Variable Speed
Air Handler
Fan only
1
Stage 1 heating
1
Stage 2 heating
1
Stage 3 heating
Emergency heat
2
Stage 1 cooling
2
Stage 2 cooling
w w w. h e a t c o n t o l l e r. c o m
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A
HSS
Variable Speed
Air Handler
Fan only
3
Stage 1 heating
3
Stage 2 heating
3
Stage 3 heating
Emergency heat
4
Stage 1 cooling
4
Stage 2 cooling
R e v. : 5 J u n e , 2 0 0 8
HSS
PSC Air Handler
Fan only
5
Stage 1 heating
5
Stage 2 heating
N/A
Emergency heat
6
Cooling
N/A
33