1652C/1653B/1654B
Users Manual
Error Codes
Various error conditions are detected by the tester and are indicated with the
icon, "Err", and an error number on the primary display. See Table 7. These
error conditions disable testing and, if necessary, stop a running test.
Error Condition
Self-Test Fails
Over-Temp
Fault Voltage
Excessive Noise
Excessive Probe
Resistance
16
Table 7. Error Codes
Code
1
Return the tester to a Fluke Service Center.
2
Wait while the tester cools down.
Check the installation, in particular, the voltage
4
between N and PE.
Switch off all appliances (Loop, RCD
5
measurements) and move the earth stakes
(earth measurement).
Put the stakes deeper into the soil. Tamp
down the soil directly around the stakes. Pour
6
water around the stakes but not at the earth
ground under test.
Figure 6. Error Display
Solution
apx032f.eps