Chassis Installation - Friedrich TEC12K34 Installation & Operation Manual

Table of Contents

Advertisement

Electrical
Rating
Tables
All 230/208 volt units are equipped
with power cords.
See Appendix
C on page 17 for wiring instructions
on 265V units.
I
NOTE:
Use Copper Conductors ONLY.
I
Wire sizes are per NEC. Check local codes
for overseas applications.
Table1
AMPS
RECEPTACLE
MANUFACTURER
250 V Receptacles and Fuse Types
15
20 *
@
30
PART NUMBERS
Hubbell
P&S
GE
Arrow-Hart
9330
5930
GE4139-3
5700
5661
5461
5661
5871
GE4069-1
GE4182-1
5661
5861
15
20
TIME-DELAY
TYPE
FUSE
30
(or HACR circuit breaker)
HACR -- Heating, Air conditioning,
Refrigeration
* May be used for 15 Amp applications
if fused for 15 Amp
NOTE: 265 volt units are permanently
connected.
Table 2
Recommended
branch circuit wire sizes*
AWG Wire size**
Nameplate
maximum circuit
breaker size
15
20
30
14
12
10
AWG --American
Wire Gauge
* Single circuit from main box
** Based on copper wire, single insulated
conductor
at 60°C
Chassis
Installation
Check to be sure wall sleeve, grille, and drain kit are installed properly before chassis installation.
Remove weatherboard
and center
support from sleeve (if still in place).
Be sure an outdoor louver is attached.
Weatherboard
I
Important:
Use a sleeve baffle kit if
installation is in a walt sleeve deeper
than 11 1/2".
Center Support
....
?1'11