Friedrich PTAC Series Installation & Operation Manual page 10

Packaged terminal air conditioners & heat pumps
Hide thumbs Also See for PTAC Series:
Table of Contents

Advertisement

920-087-04
(8-05)
Figure6
Dimensions
B
T
(6.4 cm)
rain.
Wall
A
B
Dimension*
Allow
Allow for floor
finishing
for wall
finishing
(Minimum)
Min.
Max
No Accessories
¼"
¼"
(6.4 mm)*
(6.4 mm)
---
With
Su bbase
1¾"
3W'
5"
(4.5 cm)
(8.9cm)
(12.7cm)
With
Lateral
Duct
¾"
¼"
(1.9 cm)
(6.4 mm)
---
* If more than one accessory
is to be used, use the maximum
dimension.
If the wall thickness
is more than 13¾" (35cm) -
(A + ¼" [6.4 mm]), a sleeve extension
must be used.
,
Drill two 3/16" holes through each side of the sleeve
approximately 4" from top and 4" from bottom of sleeve.
Screw four #10 x 1" screws (included) or appropriate
fasteners for your installation, through the holes in the sides
of the wall sleeve.
Apply sealant around the wall sleeve where it projects
through the inside and outside wall surfaces. Apply the
sealant to the screw heads or the tops of the fasteners used
in Step #3.
NOTE: When sealing the sleeve on the outside of the
building, be careful NOT to let the sealant block the two
condensate drain holes or the four overflow slots at the
bottom flange of the sleeve.
If the chassis and exterior grille are to be installed later, leave
the weatherboard and center support in place, otherwise
remove and dispose of them.
Provide a support lintel if the wall sleeve is installed in a
concrete or masonry wall. (See Figure 7.)
Figure7
Lintel Installation
Main studs
Jack studs
Main
Lintel
Mounting screw holes
No holes in bottom of wall
sleeve unless drain kit is used
NOTE: Construct wall opening to comply with all applicable
building codes.
10