HP Surestore Disk Array 12h - And FC60 Installation Manual page 17

Controller module installation guide
Hide thumbs Also See for Surestore Disk Array 12h - And FC60:

Advertisement

13. Verify that both controllers have the desired firmware using the front panel. The following table shows
the proper front panel commands to view the firmware revision installed:
KEY
CANCEL CANCEL
MENU
ENTER
+
+
+
+
14. Push on/off button to off position and wait for the array to turn off
15. Remove the "third" controller that was obtained is step 1. It should be in controller slot X.
16. Move the controller that is in slot Y into controller slot X.
17. Take the previously removed (original) controller and reset (disconnect and then re-connect) its
batteries both at the same time.
18. Install this previously removed (original) controller in the now empty controller slot Y.
19. Push the on/off button to the on position and allow the array to complete its initialization process. After
the initialization has completed, the front panel should say "Not Enough Disks". Check the system state
using the key strokes below. The system state should be "Not Enough Disks" with a "Firmware
Needed" warning.
KEY
CANCEL CANCEL
MENU
ENTER
+
DISPLAY
"Not Enough Disks"
"Language"
"View Settings"
"System State: Not Enough Disks"
"Primary Cntrl: X"
"SCSI ID x: ___"
"SCSI ID y: ___"
"Firmware: HP__"
DISPLAY
"Not Enough Disks"
"Language"
"View Settings"
"System State: Not Enough Disks"
"Warning: Firmware Needed"