HP StorageWorks XP1024 - Disk Array Owner's Manual page 71

Storageworks disk arrays
Hide thumbs Also See for StorageWorks XP1024 - Disk Array:
Table of Contents

Advertisement

AC line voltage requirements for the HP Disk Array XP1024 (DKC)
XP1024 hardware
Table 15 (page 71)
lists the basic AC power requirements for a 40-amp,
single-phase XP1024 DKC.
Table 15. 40-Amp, 50 or 60 Hz, Single-Phase DKC Operation
Parameter
Rated line current per power cord
(Arms)
Number of power cords
Number of circuit breakers
Recommended circuit breakers
* 60 Hz only.
Table 16 (page 71)
lists the basic AC power requirements for a 30-amp,
single-phase, XP1024 DKC.
Table 16. 30-Amp, 50 or 60 Hz, Single-Phase DKC Operation
Parameter
Rated line current per power cord
(Arms)
Number of power cords
Number of circuit breakers
Recommended circuit breakers
* 60 Hz only.
Nominal Rated Voltage (VAC)
200
208*
220
8.0
7.7
7.2
2
2
2
2
2
2
40 A 40A
40A
Nominal Rated Voltage (VAC
200
208
220
*
4.0
3.9
3.6
4
4
4
4
4
4
30 A 30 A 30 A 30 A 30 A
230
240
7.0
6.6
2
2
2
2
40A
40A
230
240
3.5
3.3
4
4
4
4
71