Table 20 Floor load rating and required clearances for a four rack configuration (right module)
(continued)
Floor Load
Rating
(kg/m2)
350
300
Notes:
1. Actual clearances for installation should be determined after consulting with construction specialist responsible for
installation building, as they could vary depending on the size/layout of the system and building conditions.
2. When various configurations of disk arrays are arranged in a row, clearance values based on the largest disk array
configuration should be used.
3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible.

Five rack configuration

This following figure and table shows the service clearances and floor load rating for a five-rack
configuration.
36
Installation requirements
Required Clearance (a+b) m
Clearance (c) m
C=0
C=0.2
1.8
1.5
3.0
2.6
C=0.4
C=0.6
1.2
1.0
2.3
2.0
C=0.6
0.6
1.5