When moving the rack, push against the rack at the 1.6 meter (63 inch) height or lower.
Exercise extra caution when moving rack sideways (racks are more stable from front to back
and when full).
For extra stability, attach your rack to other racks.
42
WARNING:
High leakage current may exist. Ensure secure earth grounding. Ensure site
electrical circuits have reliable earth grounding. Never operate products in any rack
enclosure with the ground connector disconnected. Use only the power cords with L6-20,
L6-30, or IEC-309 connectors provided with the Power Distribution Units or UPS of your
NAS solution to connect to your power source.
Ensure proper PDU installation. HP PDUs are supplied with locking washers that break
through the powder coating of the PDU and the mounting columns on the rack. Follow all of
the installation instructions for the PDUs. Check for proper grounding between PDU and
rack. To ensure a redundant ground path, each rack solution should have a minimum of two
PDUs grounded to mains, even if all components are connected through one PDU.
Caution:
Rack-optimized products are sensitive to static electricity. Wear a wrist-strap and
use a static-dissipating work surface connected to the server chassis when handling printed
circuit boards, memory devices, and processor chips or modules. Ensure that the metal wrist
strap contacts your skin and that the alligator clip is attached to a static-neutral surface.
HP StorageWorks NAS 8000 Dedicated Storage High Availability, Solution Integration Manual (SIM)