INSTALLATIUN
MOUNT
HEIGHTS & CLEARANCE
Minimum
mount
height between
range top to
hood bottom
should
be no less than 28".
Maximum
mount
height should
be no higher
than 36".
It is important
to install the hood at the
proper
mounting
height. Hoods mounted
too
low could result in heat damage
and fire haz-
ard; while hoods mounted
too high will be
hard to reach and will loose its performance
and efficiency.
If available,
also refer range manufacturer's
height
clearance
requirements
and recom-
mended
hood mounting
height above range.
DUCTING
A minimum
of 6" round or 3-1/4 x 10" rectangular
duct must be used to maintain
maximum
air flow
efficiency.
Always use rigid type metal ducts only.
Flexible ducts could restrict air flow by up to 50%.
Also use calculation
(on right) to compute
total
available
duct run when using elbows, transitions
and caps.
ALWAYS, when possible,
reduce the number or
transitions
and turns. If long duct run is required,
increase duct size from 6" to 7 or 8". Ifa reducer
is used, install a long reducer instead of a pan-
cake reducer. Reduce duct size as far away from
opening
as possible.
If turns or transitions are required:
Install as far away from opening and as far
apart, between 2, as possible.
Duct Run Calculation:
Maximum
run
6" or 3-I/4
x 10" duct
100 FT
Deduct:
each 90 Elbow used
15 FT
each 45 elbow
used
9 FT
each 6" to 3/14 x I0"
transition
used
I FT
each 3/14x
I0" to 6"
transition
used
5 FT
Side Wall Cap w/damper
30 FT
Roof Cap
30 FT
e.g.- I roof cap, 2x90 elbows,
1 45 elbow
used:
=30' + 30 _+ 9_=69'
used, 31' available
for straight
duct
runs.