REMOVING FROM STORAGE
As fans are removed from storage to be installed
in their final location, they should be protected and
maintained in a similar fashion, until the fan equipment
goes into operation.
Prior to assembly and installation of the Vektor fan
and system components, inspect the fan assembly to
make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel,
bearings, drive, motor base and accessories for
tightness.
2. Rotate the fan wheel(s) by hand and assure
no parts are rubbing. Access to the wheel is
obtained through a bolted panel located on the
side of the fan housing.
3. Ensure proper wheel settings for radial gap and
alignment. Refer to page 13.

Installation

Installations with inlet or discharge configurations that
deviate from this standard may result in reduced fan
performance. Restricted or unstable flow at the fan
inlet can cause pre-rotation of incoming air or uneven
loading of the fan wheel yielding large system losses
and increased sound levels.
System Identification Tags
Vektor fan systems may arrive in component pieces
due to shipping restrictions. Individual components
of a system have matching identification tags
which should be used to identify and assemble the
complete system.
Assembling systems
with different
identification tags
can cause reductions
in the fan(s)
performance.
Standard Fan Configurations
The following illustration identifies a typcial
configuration of the Vektor-CD system. Greenheck
also supplies custom configurations. Your system
may not be depicted in the drawing shown. Refer to
submittal drawing.
WINDBAND
NOZZLE
FAN
FH
FW
ISOLATOR

Vektor-CD Centrifugal Laboratory Exhaust
®
FLEX CONNECTOR
ISOLATION
DAMPER
PLENUM
FL
OPTIONAL
CURB SQR
ROOF CURB
PRIMARY INLET
Vektor-CD Arrangements
Vektor-CD
Single Fan System
Vektor-CD
Dual Fan System
Rigging / Assembly Instructions
1. Use standard lifting and rigging practices.
2. All lifting lugs on each component must be utilized
at the same time.
3. Plenum, blower, and windband are to be kept level
during installation.
Spreader Bar
Lifting
Lugs
Gasketing
Roof Curb / Structural Support
Vektor-CD Centrifugal Laboratory Exhaust
Vektor-CD
Opposed Fan System
Vektor-CD
Triple Fan System
Chains
Chains
Lifting
Lugs
Bypass Air
Plenum

®