Circulating Air Blower And Temperature Rise Check; Temperature Rise Check; Airflow; Calculating Airflow - Fedders FV95A054 Installating And Operation Manual

Category i natural gas and lp gas high efficiency two stage variable speed warm air furnace
Table of Contents

Advertisement

The formula for determining the furnace input via the gas
meter test dial is:
Heating Value of Gas X 3000
Input =
T
ime in Sec. for 1 cu. ft.
Where:
Input is expressed in BTU/Hr.
Bonnet Output
Airflow (CFM) =
Heating value of the gas is expressed in BTU/ ft
1.085 x
Time means time required for the test dial to indicate 1 ft
If using a gas meter with SI (metric) units:
1 ft
3
= 0.0283 m
3
1 m
3
= 35.315 ft
3
0.01 m
3
= 0.3531 ft
3
0.5 m
3
= 1.766 ft
3
IMPORTANT: NEVER ADJUST THE INPUT OF THE FURNACE
TO EXCEED THE INPUT SHOWN ON THE RATING PLATE.

Circulating Air Blower And Temperature Rise Check

TABLE 7: INPUT VALUES
The FV95A series 2-stage gas furnace is supplied with a
variable speed circulation air blower motor that will supply
HEATING VALUE OF NATURAL GAS in BTU / FT_
a constant airflow when operated within the external stat-
ic pressure limits of the unit. One of the benefits of a vari-
950
able speed circulation air blower is soft starting and stop-
44,186
46,512
ping. The motor will ramp up to normal operating speed
gradually. This will minimize noise and increase comfort by
61,860
65,116
eliminating the initial blasts of cooler air encountered with
119,302
125,581
constant speed motors. At the end of a heating or cooling
cycle, the variable speed motor will slowly ramp down
after the blower off delay timer expires. If the fan is set to
operate as a continuous blower, the motor will slowly ramp
down to the airflow set for that mode.

Temperature Rise Check

When the duct system is complete and the air filters are in
place, determine the air temperature rise of the furnace.
Insert a duct thermometer in the supply air duct. The ther-
mometer should be placed as close as practical to the fur-
nace, but out of the "line of sight" of the heat exchanger
so to prevent a false reading due to radiated heat. Ensure
that the thermometer is within the duct air-stream. Avoid
locations such as the inside radius of an elbow, etc.
Insert a duct thermometer into the return duct as close to
the furnace as possible. Ensure that the thermometer loca-
tion will be unaffected by humidifier bypass ducts, etc.
Choose a location that ensures the thermometer will be
within the air-stream of the duct. Operate the furnace long
enough to obtain a steady state condition.
When the two thermometers have stabilized, compare the
two readings. Subtract the return air duct temperature
from the supply air duct temperature. This difference is
the temperature rise.
3
T
1000
1050
48,837
68,372
131,860
INTERVAL TO
MODEL
CONSUME 1 FT_
(SECONDS)
GTM050C
72
GTM070C
51
GTM135C
27
A temperature rise within 35-65 degrees F is acceptable
when the furnace is operating with both stages of heat
on. If a higher temperature rise is desired, refer to the dip
switch settings for "Heating". This can be adjusted to
Nominal-Plus to reduce the air temperature rise or
Nominal-minus to increase the air temperature rise.

AIRFLOW

For proper furnace operation, airflow over the heat
exchanger is of utmost importance. Insufficient airflow
accelerates metal fatigue and failure in the heat exchanger
3
/sec.
and excessive airflow promotes accelerated corrosion of the
heat exchanger.
IMPORTANT: Do not bypass this step of the start up
procedures.

Calculating Airflow

There are circumstances where it may be desirable to
know the airflow delivery through the duct system, such as
when estimating the amount of airflow available for air
conditioning. This can be done by direct measurement
with electronic or sloped manometers and velometers, or
by using the formula below.
Airflow (CFM) =
Where:
1100
CFM is airflow in cubic feet per minute
∆T is the temperature rise
51,163
Bonnet output is the furnace output capacity from the
71,628
rating plate.
138,140
NOTE: The bonnet output will vary directly with the input.
If the actual input is below the stated input, the output will
be reduced in the same ratio.
Adjusting Dip Switches
If the blower speeds require adjusting, follow these steps:
TABLE 7: INPUT VALUES
HEATING VALUE OF NATURAL GAS in BTU / FT_
DISCONNECT THE ELECTRICAL SUPPLY TO THE FURNACE
900
BEFORE ATTEMPTING TO CHANGE THE BLOWER SPEED.
950
FAILURE TO DO SO COULD RESULT IN ELECTRICAL SHOCK
41,860
44,186
RESULTING IN PERSONAL INJURY OR LOSS OF LIFE.
58,605
61,860
1.
Remove the blower compartment door.
113,023
119,302
2.
Refer to the tables next page for adjusting DIP
switches/jumpers and select the appropriate settings
3.
DIP switches or jumpers are found on the integrated
furnace control board.
NOTE: some integrated furnace controls are equipped
with jumpers for blower adjustments. Please reference
"Letter" on adjustment table and control board when
making adjustment.
4.
Re-install the blower compartment door.
5.
Upon completion, recheck the furnace temperature rise
to ensure that the desired condition exists.
35
Heating Value of Gas X 3000
Input =
Time in Sec. or 1 cu. ft.
Bonnet Output
1.085 x
T
WARNING
1000
46,512
65,116
125,581
1050
1100
48,837
51,16
68,372
71,62
131,860
138,1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fv95a072Fv95a090Fv95a108

Table of Contents