Table 52 -- Pressure (psig) vs. Voltage Drop Values for Suction Pressure Transducers
PRESSURE
VOLTAGE
(psig)
DROP (V)
0
0.465
2
0.485
4
0.505
6
0.524
8
0.544
10
0.564
12
0.583
14
0.603
16
0.623
18
0.642
20
0.662
22
0.682
24
0.702
26
0.721
28
0.741
30
0.761
32
0.780
34
0.800
36
0.820
38
0.839
40
0.859
42
0.879
44
0.898
46
0.918
48
0.938
50
0.958
52
0.977
54
0.997
56
1.017
58
1.036
60
1.056
62
1.076
64
1.095
66
1.115
PRESSURE
VOLTAGE
(psig)
DROP (V)
68
1.135
70
1.154
72
1.174
74
1.194
76
1.214
78
1.233
80
1.253
82
1.273
84
1.292
86
1.312
88
1.332
90
1.351
92
1.371
94
1.391
96
1.410
98
1.430
100
1.450
102
1.470
104
1.489
106
1.509
108
1.529
110
1.548
112
1.568
114
1.588
116
1.607
118
1.627
120
1.647
122
1.666
124
1.686
126
1.706
128
1.726
130
1.745
132
1.765
134
1.785
PRESSURE
(psig)
136
1.804
138
1.824
140
1.844
142
1.863
144
1.883
146
1.903
148
1.922
150
1.942
152
1.982
154
1.982
156
2.001
158
2.021
160
2.041
162
2.080
164
2.080
166
2.100
168
2.119
170
2.139
172
2.159
174
2.178
176
2.198
178
2.218
180
2.237
182
2.257
184
2.277
186
2.297
188
2.316
190
2.336
192
2.356
194
2.375
196
2.395
198
2.415
200
2.434
202
2.454
VOLTAGE
DROP (V)
PRESSURE
(psig)
204
206
208
210
212
214
216
218
220
222
224
226
228
230
232
234
236
238
240
242
244
246
248
250
252
254
256
258
260
262
264
266
268
270
VOLTAGE
DROP (V)
2.474
2.493
2.513
2.533
2.553
2.572
2.592
2.612
2.631
2.651
2.671
2.690
2.710
2.730
2.749
2.769
2.789
2.809
2.828
2.848
2.868
2.887
2.907
2.927
2.946
2.966
2.986
3.005
3.025
3.045
3.065
3.084
3.104
3.124
MAJOR
SYSTEM
COMPONENTS
General
-- The 48/50PG single-package rooftop units con-
tain the (bmjbrtLink
TM
electronic conm)l system that monitors
all operations of the rooftop. The control system is composed
of several main control components and available fiactory-
installed options or field-installed accessories as listed in sec-
tions below. See Fig. 14-19 for the control and power schemat-
ics. Figures 20 and 21 show the layout of the control box, unit,
and thermistor and transducer locations.
Main Base Board (MBB)
-- See Fig. 22 and Table 53.
The MBB is the center of the (bmJbrtLink control system. It
contains the major portion of the operating sot_vare and con-
trois the operation of the unit. The MBB continuously monitors
input/output channel information received t_om its inputs mad
fiom the Economizer Control Board (ECB). The MBB re-
ceives inputs fiom thermistors and transducers. The MBB also
receives the Current Sensor inputs for compressors and other
discrete or diNtat inputs. The MBB reads space temperature
(SPT) tiom either a T-55, T-56 or T-58 device and space tem-
perature ofl;et (SPTO) fiom a 1-56 device. See Field-Installed
Accessories section on page 82. The MBB controls 9 relays.
NOTE: The Main Base Board (MBB) has a 3-position instance
jmnper that is thctory set to ' 1'. Do not change this setting.
Economizer
Control
Board (ECB) -- The ECB con-
trols the economizer actuator. See Fig. 23 and Table 54. The
control
signal
from
the
ECB
uses
either
the
MFT
(Multi-Function Technology) COlrnnunication protocol or a 4 to
20 mA
output signal as defned
by the confignration
Configumtion-->ECON-->E.CTL.
The
ECB
has inputs
for
Indoor Air Quality (IAQ),
Outdoor
Air Quality
(OAQ), mad
enthalpy. It also controls two power exhaust outputs.
By digitally colrnnunicating
with the ECB, the economizer
actuator is able to provide the dmnper position and diagnostic
information
to
the
ComJbrtLink
controller.
The
damper
position is displayed at Outputs--+ECON--+ECAP
Diagnostic
information
is displayed
via Alert
T414. More
information
about these
alarms
is contained
in the Atanns
and Alerts
section.
NOTE:
The
Economizer
Control
Board
(ECB)
has
a
&position
DIP switch that is thctory set to ON (towards
the
center of the board). Do not change
this setting.
Integrated
Gas Control
(IGC) Board -- The IGC
is provided on gas heat units. See Table 55 and Fig. 24. The
IGC controls the direct spark ignition system and monitors the
rollout switch, limit switch, and induced-draft motor Hall
Efl_ct switch. The IGC is equipped with an LED (light-
emitting diode) tbr diagnostics. See the Troubleshooting
section for more information.
Low Voltage
Terminal
Strip
(TB2) -- This circuit
board provides a connection point bewveen the major control
boards and a majority of the field-installed accessories. See
Fig. 25 and Table 56. The interthce connection for the Carrier
Comfort Newvork¢<3 (CCN) colrnnunication and interthce con-
nection for the Local Equipment Newvork (LEN) communica-
tions are also located on the low voltage tenninat strip.
67