Table 44 -- Cooling
Service Analysis
PROBLEM
Compressor
and Fan Will Not Start.
Compressor
Cycles (other than
normally
satisfying thermostat).
Compressor
Operates Continuously,
Excessive
Condenser
Pressures.
Condenser
Fans Not Operating,
Excessive
Suction Pressure,
Suction Pressure Too Low.
LEGEND
CB
--
Circuit Breaker
TXV
--
Thermostatic
Expansion Valve
CAUSE
Power failure.
Fuse btown or circuit breaker tripped
Check CB1, CB2, and
CB3
Disconnect
off
Compressor
time guard to prevent short cycling
Thermostat
or occupancy
schedule set point not calting for
Cooling
Outdoor temperature
too tow.
REMEDY
Call power company
Replace fuse or reset circuit breaker.
Insufficient
line voltage.
Active alarm.
Unit undersized
for load
Thermostat
or occupancy
schedute set point too low.
Dirty air fitters.
Low refrigerant charge
Condenser
coil dirty or restricted.
Loose condenser thermistors
Dirty condenser coil
Refrigerant
overcharge.
Faulty TXV.
Condenser
air restricted or air short cycling
Restriction
in liquid tube.
No Power to contactors.
High heat load
Faulty TXV.
Refrigerant
overcharged.
Dirty air fitters
Low refrigerant charge
Faulty TXV.
Insufficient
evaporator
airflow
Temperature
too low in conditioned
area (low return-air
temperature).
Power disconnect.
Check using ComfortLink
TM
Scrolling Marquee.
Check using ComfortLink
ScroIling Marquee
Check Compressor
Lockout Temperature
using
ComfortLink
ScroIling Marquee.
Active alarm.
Check active alarms using ComfortLink
Scrolling
Marquee
Determine
cause and correct.
Check active alarms using ComfortLink
Scrolling
Marquee
Decrease
load or increase size of unit.
Reset thermostat
or schedule set point.
Replace filters.
Check pressure, locate leak, repair, evacuate, and recharge.
Clean coit or remove restriction.
Tighten thermistors.
CIean coil
Recover excess refrigerant
1 Check TXV bulb mounting
and secure tightly to suction
tine and insulate.
2 Replace TXV (and filter drier) if stuck open or closed.
Determine
cause and correct.
Remove restriction
Fuse blown or plug at motor loose
Check for sources and eliminate
1 Check TXV bulb mounting
and secure tightly to suction
Iine and insulate.
2 Replace TXV (and filter drier) if stuck open or closed.
Recover excess refrigerant
Replace air fitters.
Check pressure, locate leak, repair, evacuate, and recharge.
1 Check TXV bulb mounting
and secure tightly to suction
line and insulate.
2 Replace TXV (and filter drier) if stuck open or closed.
Check belt tension. Check for other restrictions.
Reset thermostat
or occupancy
schedule.