Table 48 -- IGC Board LED Alarm Codes
LED FLASH
DESCRIPTION
ACTION TAKEN BY
RESET METHOD
PROBABLE
CAUSE
CODE
CONTROL
On
Normal Operation
--
--
--
Off
Hardware Faiture
No gas heating
--
Loss of power to the IGC Check 5 amp fuse on IGC,
)ower to unit, 24V circuit breaker, transformer,
and wir-
ing to the IGC.
1 Flash
Indoor Fan On/Off Delay
5 seconds subtracted from On
Power reset
High temperature
limit switch opens during heat
Modified
delay,
exchanger warm-up period before fan-on deIay expires
5 seconds
added to Off delay
High temperature
limit switch opens within
(3 min max)
10 minutes of heat call (W) Off
See Limit Switch Fautt
2 Flashes
Limit Switch Fault
Gas vaIve and igniter Off
Limit switch closed, or heat
High temperature
limit switch is open
Check the opera-
Indoor fan and inducer On
call (W) Off
tion of the indoor (evaporator)
fan motor. Ensure that the
supply-air temperature
rise is within the range on the
unit nameplate
Check wiring and limit switch operation.
3 Flashes
Flame Sense Fault
indoor fan and inducer On
Flame sense normal
The IGC sensed a flame when the gas vaIve should be
Power reset for LED reset
closed. Check wiring, flame sensor, and gas valve oper-
ation
4 Flashes
Four Consecutive
Limit Switch
No gas heating
Heat caII (W) Off
4 consecutive
limit switch faults within a single call for
Fault
Power reset for LED reset
heat. See Limit Switch Fault.
5 Flashes
Ignition Fault
No gas heating
Heat caII (W) Off
Unit unsuccessfully
attempted
ignition for 15 minutes.
Power reset for LED reset
Check igniter and flame sensor electrode spacing, gaps,
etc Check flame sense and igniter wiring. Check gas
valve operation and gas supply.
6 Flashes
Induced Draft Motor Fault
if heat off: no gas heating
Inducer sense normal, or
Inducer sense On when heat call Off, or inducer sense
If heat on: gas valve Off and
heat call (W) Off
Off when heat call On. Check wiring, voltage, and oper-
inducer On.
ation of IGC motor Check speed sensor wiring to IGC
7 Flashes
Rotlout Switch Lockout
Gas valve and igniter Off
Power reset
Rollout switch has opened
Check gas valve operation.
Indoor fan and inducer On
Check induced-draft
blower wheel is properly secured to
motor shaft.
8 Flashes
Internal Controt Lockout
No gas heating
Power reset.
IGC has sensed internal hardware or software error
If
fault is not cteared by resetting 24 v power, replace the
IGC.
9 Flashes
Temporary Software Lockout
No gas heating
1 hour auto reset, or power
Electrical interference
is disrupting the IGC
reset,
software
LEGEND
IGC
--
Integrated Gas Unit Control
LED
--
Light-Emitting
Diode
NOTES:
1 There is a 3-second
pause between alarm code displays
2 If more than one alarm code exists, atl applicable
alarm codes wiIt be dis-
played in numerical sequence.
3 Alarm codes on the IGC witl be lost if power to the unit is interrupted.
Table 49 -- Electric Heat Service Analysis
PROBLEM
CAUSE
REMEDY
Heat Will Not Turn On.
Active alarm.
Check active alarms using ComfortLink
TM
Scrolling Marquee.
No power to unit.
Check power supply, fuses, wiring, and circuit breakers.
Unit is in minimum heat off-time, or minimum cool-heat
Check using ComfortLink
Scrolling Marquee
changeover
time
Thermostat
or occupancy
schedule setpoint not calling for
Check using ComfortLink
Scrolling Marquee
heating.
Heat forced off in Service Test mode.
No 24 vac at heater contactor
Check using ComfortLink
Scrolling Marquee. Turn Service Test
mode off.
Check transformer
and circuit breaker.
Check auto-reset
timit switches on heater
Check manual-reset
timit switch (LS) on heater.
Check minimum
airflow Check limit switch when it is coot,
replace if open
Replace air filters
Atlow time for W2 to energize.
Open temperature
timit switch on heater.
Inadequate
Heating.
Dirty air fitters.
Thermostat
or occupancy
schedule setpoint only calling
forWl.
Heat undersized for load
Decrease
load or increase size of heater.
Restricted airflow
Remove restriction.
Too much outdoor air
Check economizer
position and configuration
Adjust minimum
position.
Limit switch cycles heaters.
Check rotation of blower and minimum airflow
Bad heater elements
Power off unit and remove high vottage wires. Check resistance
of element, replace if open
Heat Will Not Turn Off.
Unit is in minimum heat on-time
Check using ComfortLink
Scrolling Marquee
Thermostat
or occupancy
schedute setpoint stilt calling for
Check using ComfortLink
Scrolling Marquee
heating.
Heat forced on in Service Test mode.
Check using ComfortLink
Scrolling Marquee. Turn Service Test
mode off.
Heater contactor faiIed.
Power off unit Check contactor and reptace if closed
62