Carrier 48PG03-14 Installation Instructions

Single-package rooftop units two-position damper accessory

Advertisement

Quick Links

Part Numbers: CRTWOPOS007A00, CRTWOPOS008A00
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
GENERAL
IMPORTANT: Read these instructions completely before
attempting to install the accessory two-position damper.
The accessory two-position damper is designed for use on
units without economizers.
The two-position damper accessory allows the unit to
control the outside-air dampers by opening the dampers
whenever the indoor fan is operating and closing the dampers
when the indoor fan is off. There is no modulation associated
with the two-position damper assembly.
PACKAGE USAGE
UNIT
PART NUMBER
48/50PG
03-07
CRTWOPOS007A00
08-14
CRTWOPOS008A00
PACKAGE CONTENTS
QTY
1
Hardware Bag
1
Bottom Panel
1
Top Panel/Damper Assembly
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Book 1
1
4
4
Tab
1a 1b 6a 6b

Installation Instructions

SHIPPING
WEIGHT (lb)
65
85
CONTENTS
Catalog No. 534-80173
Printed in U.S.A.
Single-Package Rooftop Units
Two-Position Damper Accessory
Turn off unit power and lockout. Electrical shock and per-
sonal injury could result.
To install the two-position damper, perform the following:
1. Make sure power supply is turned off and lockout tag is
installed.
2. Unscrew and remove the front cover panel on the return
end of the unit to expose the return section of the unit. See
Fig. 1. Discard panel and save screws.
Cover the duct opening as a precaution so objects cannot
fall into the return duct opening.
3. Install the bottom panel over the return air compartment.
Use screws saved from Step 2. See Fig. 1.
4. Connect the plug from the two-position damper actuator
to the 6-pin economizer/two-position damper plug in the
return air compartment of the unit. See Fig. 1 and 2.
5. Adjust two-position damper to desired setting. Two-
position damper performance is shown in Fig. 3 and 4. To
adjust damper, locate the adjustable stop on the actuator.
Loosen but do not remove the screw. Align pointer with
desired setting based on the return duct static pressure and
airflow. Tighten screw.
6. Install the top panel assembly over the top section of the
return air compartment. The top panel assembly should
overlap the bottom panel installed in Step 3. Use screws
provided. See Fig. 1.
7. Remove lockout tag and restore power to unit.
Form 48/50PG-4SI
48/50PG03-14
INSTALLATION
Pg 1
10-04
Replaces: New

Advertisement

loading

Summary of Contents for Carrier 48PG03-14

  • Page 1: Installation Instructions

    48/50PG03-14 Single-Package Rooftop Units Two-Position Damper Accessory Installation Instructions Part Numbers: CRTWOPOS007A00, CRTWOPOS008A00 SAFETY CONSIDERATIONS INSTALLATION Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo- nents. Only trained and qualified service personnel should Turn off unit power and lockout.
  • Page 2 ECONOMIZER/TWO-POSITION DAMPER PLUG FROM HVAC UNIT FRONT COVER PANEL PLUG FROM TWO-POSITION DAMPER ACTUATOR TOP PANEL / DAMPER ASSEMBLY OUTSIDE AIR HOOD FOR TWO-POSITION DAMPER BOTTOM PANEL DIMENSIONS (in.) UNIT ACCESSORY NOTE: Outside air hood is shown removed from top 48/50PG panel.
  • Page 3 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.40 0.35 0.30 0.25 0.20 0.15 0.10 0.05 0.00 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 CFM (Cubic Feet Per Minute) *Two-position damper position (outdoor air marking on actuator). Fig.
  • Page 4 Copyright 2004 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 534-80173 Printed in U.S.A. Form 48/50PG-4SI Pg 4 10-04 Replaces: New...