6.3.1

Identify the Zone as Connected

To make use of the zone ZN1, you must specify it as Connected (Y). By
default, ZN1 is Not connected (N). See 3.1 - Connecting Leak Detec-
tion Cable Inputs for instructions on connecting the cable to this
zone.
• From the Setup Zone 1 Menu, choose Connected, as shown at
right, and press Enter .
• To change this feature, use the arrows
nected) or N (No - Not connected), then press Enter .
6.3.2

Change Zone Label

ZN1 has a default label (Zone 1) that you may change to a more
descriptive name, such as "SRVR RM1." The label may consist of up to
eight characters (see Table 7 for valid characters).
• From the Setup Zone 1 Menu, choose Label, then press Enter .
• To change the label, which may consist of up to eight characters:
• Use the arrows
• Press Enter
• When finished, press Enter
6.3.3

Change Units Label

You may specify measurement units as feet (FT) or meters (M). The
default designation is FT (feet). The same measurement unit will
apply to both zones. For example, if you choose FT for Zone 1, Zone 2
will display in FT also.
• From the Setup Zone 1 Menu, choose Units, then press Enter .
• To change the units label:
• Use the arrows
• Press Enter .
to choose a character.
to advance to the next character position.
again.
to choose FT (feet) or M (meters).
26
to choose Y (Yes - Con-
System and Control Options
Setup Zone 1 Menu
SETUP ZN1 ZONE 1
> CONNECTED:
N
LABEL: ZONE 1
=NEXT
=SELECT
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA
Zone Connected
IS CABLE CONNECTED
TO THIS ZONE? Y
=Y/N
=END
Setup Zone 1 Menu
SETUP ZN1 ZONE 1
CONNECTED:
Y
> LABEL: ZONE 1
=NEXT
=SELECT
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA
Change Zone Label
CHANGE ZONE LABEL
LABEL: ZONE 1
=SELECT
=NEXT/END
Setup Zone 1 Menu
SETUP ZN1 ZONE 1
CONNECTED:
Y
LABEL: ZONE 1
=NEXT
=SELECT
> UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA
Change Units Label
CHANGE UNITS
UNITS: FT
=FT/M
=END